当前位置: X-MOL 学术J. Clean. Prod. › 论文详情
Our official English website, www.x-mol.net, welcomes your feedback! (Note: you will need to create a separate account there.)
Energy Consumption Analysis in Wastewater Treatment Plants Using Simulation and SCADA system: Case Study in Northern Taiwan
Journal of Cleaner Production ( IF 9.7 ) Pub Date : 2020-09-18 , DOI: 10.1016/j.jclepro.2020.124248
Wu-Yang Sean , Ya-Yun Chu , Lili Lorensia Mallu , Jian-Gu Chen , Han-Yang Liu

Energy consumption is a crucial aspect in wastewater treatment plants. Biological processes using aeration systems contribute significantly to energy usage. Tao-bay plants in northern Taiwan are recent plants that have not introduced automated control on aeration systems yet. The use of numerical methods aims to predict optimized airflow rate and energy consumption and to provide references for the first-phase plant operation. In this study, a steady-state modeling using GPS-X 7.0 is presented. Measured monthly data in a yearly basis for parameters such as BOD, COD, total N, N-NH4+, and total P were used as the input data. The measured effluent concentrations for these parameters were compared with numerically calculated values for calibration purposes. An empirical correlation is also proposed for an alternative calculation of airflow and relative electricity consumption. A supervisory control and data acquisition (SCADA) system that consisted of current and water quality sensors with an online interface was developed to monitor the aeration system of the case-study plant. Selected real-time data for DO and electricity usage related to the biological treatment were recorded in the cloud server and used for verifying and compensating existing data measured in the plant. According to the monthly energy-consumption data for Tao-bay plant in 2018, the energy-saving rate predicted using the GPS-X model was approximately 20 %, which is consistent with the global values (18–21 %) of the plant operating in the range of 50,000–10,000 CMD. Moreover, when adjusting DO every 1 mg/L to fit a sewage-discharge criterion, the energy-saving rate was approximately 5–7 %.

更新日期:2020-09-20
down
wechat
bug