Convective boiling of R-410A in 5.0 and 7.0 mm outer diameter microfin tubes
Experimental Heat Transfer ( IF 2.5 ) Pub Date : 2019-07-15 , DOI: 10.1080/08916152.2019.1641168
Nae-Hyun Kim 1
Affiliation  

ABSTRACT Although microfin tubes are widely used in refrigeration and air-conditioning industries, relatively little data are available for small diameter tubes. In the present study, 7.0 and 5.0 mm outer diameter (O.D.) microfin tubes were tested for a range of mass flux (from 50 to 250 kg/m2s) and vapor quality (from 0.2 to 0.8). The saturation temperature was 8°C and the heat flux was 3.0 kW/m2. This heat flux is quite small, and existing investigations have not been gone to this low heat flux. Results showed that an optimum behavior was observed for the enhancement factor. It increased as mass flux increased up to 150 kg/m2s, and then decreased with a further increase of mass flux. The penalty factors were larger than 1.0 except at the lowest mass flux of 50 kg/m2s. Possible reasoning was provided based on flow patterns of the microfin and the smooth tube. The enhancement factor ranged from 1.24 to 1.93 for the 7.0 mm microfin tube, and 1.63 to 3.26 for the 5.0 mm microfin tube. The penalty factor ranged from 0.82 to 1.11 and from 0.48 to 1.39 for the 7.0 mm and the 5.0 mm microfin tube, respectively. Larger high fin height of the 5.0 mm microfin tube may be responsible for the larger enhancement and penalty factor of the 5.0 mm microfin tube. Comparison with predictions by existing correlations revealed that 7.0 mm microfin tube data were reasonably predicted. However, 5.0 mm microfin tube data were generally underpredicted, probably due to the large fin height of the 5.0 mm microfin tube.

中文翻译:

R-410A 在 5.0 和 7.0 毫米外径微翅片管中的对流沸腾

摘要 虽然微翅片管广泛应用于制冷和空调行业,但可用于小直径管的数据相对较少。在本研究中,7.0 和 5.0 毫米外径 (OD) 微翅片管在一系列质量通量(50 至 250 kg/m2s)和蒸汽质量(0.2 至 0.8)范围内进行了测试。饱和温度为 8°C,热通量为 3.0 kW/m2。这种热通量非常小,现有的研究还没有针对这种低热通量进行研究。结果表明,对于增强因子观察到最佳行为。它随着质量通量增加到 150 kg/m2s 而增加,然后随着质量通量的进一步增加而降低。除了最低质量通量 50 kg/m2s 外,惩罚系数大于 1.0。根据微翅片和光滑管的流动模式提供了可能的推理。7.0 毫米微细管的增强系数范围为 1.24 至 1.93,5.0 毫米微细管的增强系数为 1.63 至 3.26。对于 7.0 毫米和 5.0 毫米微型鳍片管,惩罚系数的范围分别为 0.82 至 1.11 和 0.48 至 1.39。5.0 mm 微细管的较大的高翅片高度可能是 5.0 mm 微细管的更大增强和惩罚因子的原因。与现有相关性预测的比较表明,7.0 毫米微鳍管数据是合理预测的。然而,5.0 毫米微翅片管数据通常被低估,可能是由于 5.0 毫米微翅片管的翅片高度较大。0 毫米微鳍管。对于 7.0 毫米和 5.0 毫米微型鳍片管,惩罚系数的范围分别为 0.82 至 1.11 和 0.48 至 1.39。5.0 mm 微细管的较大的高翅片高度可能是 5.0 mm 微细管的更大增强和惩罚因子的原因。与现有相关性预测的比较表明,7.0 毫米微鳍管数据是合理预测的。然而,5.0 毫米微翅片管数据通常被低估,可能是由于 5.0 毫米微翅片管的翅片高度较大。0 毫米微鳍管。对于 7.0 毫米和 5.0 毫米微型鳍片管,惩罚系数的范围分别为 0.82 至 1.11 和 0.48 至 1.39。5.0 mm 微细管的较大的高翅片高度可能是 5.0 mm 微细管的更大增强和惩罚因子的原因。与现有相关性预测的比较表明,7.0 毫米微鳍管数据是合理预测的。然而,5.0 毫米微翅片管数据通常被低估,可能是由于 5.0 毫米微翅片管的翅片高度较大。与现有相关性预测的比较表明,7.0 毫米微鳍管数据是合理预测的。然而,5.0 毫米微翅片管数据通常被低估,可能是由于 5.0 毫米微翅片管的翅片高度较大。与现有相关性预测的比较表明,7.0 毫米微鳍管数据是合理预测的。然而,5.0 毫米微翅片管数据通常被低估,可能是由于 5.0 毫米微翅片管的翅片高度较大。
更新日期:2019-07-15
down
wechat
bug