当前位置: X-MOL 学术Fusion Eng. Des. › 论文详情
Our official English website, www.x-mol.net, welcomes your feedback! (Note: you will need to create a separate account there.)
Concept design of 100 kA hybrid DC breaker on China fusion engineering test reactor
Fusion Engineering and Design ( IF 1.9 ) Pub Date : 2020-09-01 , DOI: 10.1016/j.fusengdes.2020.111740
Hu Xingguang , Li Hua , Song Zhiquan , Ren Zhigang , Wang Shusheng , Tang Cunwen , Fu Peng

Abstract China Fusion Engineering Test Reactor (CFETR) is the next device for the Chinese magnetic confinement fusion program, which is now under conceptual design phase. This paper describes the concept design of the high current hybrid breaker for the quench protection of superconducting magnets. The rated currents and maximum reapplied interruption voltages for breaker are 100 kA and 20 kV. The concept solution design of DC breaker is presented, which is mainly composed of a mechanical main switch with three levels contacts for conducting the continuous current, and a solid-state switch in parallel for current transferring. The design principles of each part and the preliminary results are given respectively. Finally, two test platforms were built to verify the calculation and design. Compared with the traditional oscillation zero-point DC breaker, the hybrid breaker topology can improve the dielectric strength recovery speed of mechanical switch and reduce the whole operation time. It is more suitable for fast current interruption at heavy DC current level.
更新日期:2020-09-01
down
wechat
bug