Effective Hold-Up Time Extension Method Using Fan Control in Server Power Systems
IEEE Transactions on Industrial Electronics ( IF 7.5 ) Pub Date : 8-14-2019 , DOI: 10.1109/tie.2019.2934032
Jaeil Baek , Jae-Bum Lee , Jae-Kum Kim

This letter proposes a simple and effective hold-up time extension method for server power systems, in which the fan is only turned off during the hold-up time with ac input loss. Due to the elimination of the fan power in the proposed method, the efficiency of the dc-dc converter increases during the hold-up time; thus, the energy stored in the link capacitor decreases less sharply, compared with the conventional method. That is, the hold-up time can be extended without additional devices, volume increase, and operational change of the dc-dc converter, maintaining high efficiency and high power density. The effectiveness of the proposed method is verified by a prototype with 90-264 Vac,rms input, 800 W/12 V output specifications of the server power supply.