1 Introduction

Researchers have investigated the earthquake-induced pounding phenomenon, especially the influence of the impact force as an unexpected additional force for structures [1,2,3,4]. The importance of these studies is related to the fact that many buildings were constructed without sufficient in-between Separation Distance (SD) and pounding between them during earthquakes can impose crucial damages or total destruction. In addition, the design process of structures in the past neglected this external force, as the minimum SD between adjacent structures was not considered in the old seismic codes. Neglecting the SD between the newly constructed buildings also takes place because of the land price in populated cities and lack of a proper monitoring system of construction of buildings [1,2,3]. There are many examples of such a situation, as it can be seen in Fig. 1.

Fig. 1
figure 1

Newly constructed adjacent buildings without sufficient SD, and with different base and floors levels (Qazvin, Iran)

Although the current seismic codes prescribe a minimum SD, some factors such as an irregular plan or different center of rigidity, which can lead to a torsional movement, make this distance ineffective. Researchers categorized structural pounding as: the floor-to-floor or the floor-to-column pounding [4,5,6,7,8], pounding due to difference in weight of adjacent structures [5, 9, 10], eccentric or non-eccentric pounding [11, 12], and pounding between unequal-height buildings in series [13, 14].

The nature of the earthquake-induced pounding phenomenon is a highly-complex engineering problem that should be solved by engineers. Due to this complexity, researchers proposed some ways to control collisions between adjacent structures. One possible solution is to increase the stiffness of the structural members and finally reduce the lateral displacements. Although this approach can be used in all types of structures, this may impose the increase in the construction cost and architectural issues. Therefore, researchers proposed using energy dissipation devices due to their ability to control both displacements and accelerations that are the main features of the pounding phenomenon [15,16,17]. Raheem [18] conducted the parametric study on the adjacent buildings exposed to earthquakes using linear and nonlinear contact models for different SDs. He proposed to use a shock absorber that reduces the acceleration peaks and finally the impact force. In a more general work, Raheem et al. [19] investigated the effects of eccentric alignment of three, six, and twelve-story adjacent structures under nine earthquakes using a viscoelastic impact model. Their results confirm that the eccentric alignments make the design more complicated and the corners of buildings play a key role against the torsional response of eccentric pounding. Impact-absorbing materials were also considered and a number of studies were carried out using polystyrene bumpers and polymer elements [20,21,22] and rubber shock absorbers [23, 24]. To overcome the pounding impact, Jankowski and Mahmoud [25] connected the three-story adjacent structures with link elements using spring, dashpots, and viscoelastic elements. The results showed that using viscoelastic elements reduced the peak displacement response of structures compared to dashpot or spring elements applied alone. Regarding this approach, other studies were also carried for viscous dampers (VDs) [26,27,28,29,30,31], tuned mass dampers [32], friction dampers [33], and multi-link viscoelastic elements [34] installed at the floor levels of buildings where larger probability of collisions is expected. The Linear or Nonlinear Viscous Dampers (LVDs or NVDs) may have different properties. Martinez-Rodrigo and Romero [35] compared the use of the LVDs and NVDs, and found out that the larger reduction occurred in the case of LVDs while the NVDs achieved smaller damping force. Increasing the number of VDs would not certainly be related to their efficiency [36, 37], while the distribution of VDs had significant effects on structural modal properties [38]. Adding LVDs at all floor levels of the adjacent steel and reinforced concrete structures were proposed by Kazemi et al. [39]. This approach eliminates the sudden changes in impact force, and therefore reduces the possibility of structural damages due to the pounding phenomenon.

The purpose of this study is to investigate an optimal placement of LVDs or NVDs between Steel and RC Moment-Resisting Frames (SMRFs and RC MRFs) prone to earthquake-induced pounding considering the optimized cost of implementation and the seismic limit-state capacity performance level as targets. Therefore, the seismic performance levels of both adjacent structures were investigated, while implementing LVDs or NVDs can affect the seismic behavior of both of them. In addition, based on the results of this study, modification factors for retrofitted structures are determined that can provide a practical tool for estimating proposed retrofitting strategy on the newly constructed or existing structures.

2 Methods of modeling

2.1 Modeling approach of adjacent buildings

To study the pounding phenomenon, the 3-, 5-, and 9-story SMRFs and RC MRFs were considered to be constructed in California with seismic design parameters of SDS = 1.0 g and SD1 = 0.6 g and soil type of D (see Fig. 2 for their structural plan). To model the structures, the seismic codes of ASCE 7-16 [40], ANSI/AISC 360-16 [41], ANSI/AISC 341-16 [42], and ACI 318-14 [43] were used. The design coefficients and factors for assumed structures were considered according to the seismic code of ASCE 7-16 [40] (Table 12.2-1), having dead and live loads of 8.379 kN/m2 and 2.39 kN/m2, respectively. Based on the procedures of modeling used by Kitayama and Constantinou [44] and Haselton and Deierlein [45], it is possible to model three-dimensional building by a two-dimensional structure. For this purpose, the main columns of MRFs are used (columns with thick blue lines in Fig. 2 show the MRFs in the X direction), which are connected to the leaning column taking into account the other gravity columns effects. Using the leaning column provides the possibility of considering the P-delta effects with acceptable accuracy of modeling (e.g. see [7, 9, 46]). For modeling structures, the concrete compressive strength of 34.5 MPa, the steel yield strength and Young’s modulus of 345 MPa and 200 GPa, respectively, were assumed in the analysis. Figures 3 and 4 show the three-dimensional view of the 3-, 5-, and 9-story SMRFs and RC MRFs, respectively.

Fig. 2
figure 2

Considered plan for modeling steel and RC MRFs

Fig. 3
figure 3

Three-dimensional view of the 3-, 5-, and 9-story SMRFs

Fig. 4
figure 4

Three-dimensional view of the 3-, 5-, and 9-story RC MRFs

For SMRFs, the moment-rotation behavior of the structural elements were defined considering a nonlinear rotational spring at both ends of each member. The behavior of the spring was simulated based on the modified Ibarra–Krawinkler bilinear-hysteretic model (for more detail see [39, 46]) and it was assigned using the zero-length element. The Ibarra–Krawinkler model can simulate the cyclic deterioration including unloading and reloading stiffness, strength and post-capping strength. Figure 5 presents the two-dimensional model and the modified Ibarra–Krawinkler model used for defining the nonlinear behavior of elements. It should be noted that 316 specimens were used to calibrate the model with wide range of W-sections [39,40,41,42,43,44,45,46]. Therefore, it is possible to calculate the parameters of hysteresis curves using formula introduced by Lignos and Krawinkler [47].

Fig. 5
figure 5

Two-dimensional model and the modified Ibarra–Krawinkler model used for defining the nonlinear behavior of elements

To model beams and columns of RC MRFs, a trilinear backbone curve of deterioration model, mainly developed by Ibarra et al. [48] and implemented in Opensees [49] software by Altoontash [50], was used. This model can capture the modes of cyclic degradation and collapse states. Two main sources were used for determining the model parameters: the first one is based on the relationships introduced by Fardis and Biskinis [51], and the second one is based on the experimental specimens of columns investigated by Berry et al. [52]. A number of studies were performed based on this model to capture the seismic collapse capacity of the RC MRFs (e.g. see [39, 53, 54]). Structural documentation of the columns and beams of RC MRFs and SMRFs are presented in Tables 1 and 2.

Table 1 Structural documentation of the columns of RC MRFs
Table 2 Structural documentation of SMRFs and RC MRFs

2.2 Impact contact element

To simulate the structural pounding phenomenon, researchers used different element force models that can precisely model the impact force with high accuracy. The viscoelastic contact element (Kelvin-Voigt element) with high acceptable accuracy was used in this study [54, 55]. The implementation of viscoelastic contact element was validated by Kazemi et al. [5] using the following formula:

$$F(t) = K_{{{\text{imp}}}} \delta (t) + C_{{{\text{imp}}}} \dot{\delta }(t)$$
(1)
$$C_{{{\text{imp}}}} = 2\xi \sqrt {K_{{{\text{imp}}}} \frac{{m_{1} m_{2} }}{{m_{1} + m_{2} }}}$$
(2)
$$\xi = \frac{ - \ln (e)}{{\sqrt {\pi^{2} + \left( {\ln e} \right)^{2} } }}$$
(3)

where \(F(t)\) is the impact force, Cimp and Kimp are impact damping and stiffness coefficients, and relative deformation and velocity are expressed as \(\delta (t)\) and \(\dot{\delta }\left( t \right)\). m1 and m2 are masses of particular stories of adjacent structures, and ξ is the impact damping ratio [56,57,58]. The coefficient of restitution, e, was assumed equal to 0.65 (e.g. see [39, 46, 54,55,56,57,58,59]). According to Polycarpou et al. [12] approach for modeling the three-dimensional adjacent structure, the dimensionless impact stiffness, Ki, in the contact region can be determined as follows:

$$K_{i} = \left[ {\frac{{1 - \nu_{1}^{2} }}{{E_{{\text{Dyn,1}}} }} + \frac{{1 - \nu_{2}^{2} }}{{E_{{\text{Dyn,2}}} }}} \right]^{ - 1} $$
(4)
$$E_{{\text{Dyn, i}}} = 5.82\left( {E_{{{\text{Static}}, i}} } \right)^{0.63}$$
(5)

where νi and EDyn, i are the Poisson's ratio and the dynamic elastic modulus of contact material. Considering the EStatic = 21 GPa and νi = 0.2 are used for normal strength concrete, the dimensionless impact stiffness, Ki, can be calculated from Eqs. 4 and 5 as equal to Ki = 209.6 × 105 kN/m2. Moreover, assuming the half of structural plan (see Fig. 2) in pounding condition (9.144 m), the impact damping and stiffness coefficients, Cimp and Kimp, can be obtained from the equations equal to Ck = 7576 kNs/m and Kimp = 19.17 × 107 kN/m, respectively.

2.3 Models of pounding

Modeling pounding is a very complicated process, including factors such as the local deformation effects, the yielding area, the material of impact area and ductility effects. Although these factors can complicate the modeling process, it has been seen that different damping coefficients and impact stiffness do not significantly affect the results [60]. Hence, the determined values can be approximately considered as appropriate values for the analysis.

To consider the allowable SD, the approach proposed by ASCE 7-16 [40] was used. The adjacent buildings should be separated by the allowable SD, which can be calculated as follows:

$${\text{SD}} = \sqrt {\left( {\frac{{C_{{\text{d}}} \cdot \delta_{{\text{M}}} }}{I}} \right)_{1}^{2} + \left( {\frac{{C_{{\text{d}}} \cdot \delta_{{\text{M}}} }}{I}} \right)_{2}^{2} }$$
(6)

where δM is the maximum inelastic response displacement and Cd and I are the deflection amplification factor and the importance factor, respectively. δM for both RC MRFs and SMRFs can be calculated from the nonlinear static analysis (i.e. pushover) having the lateral load distribution of the first mode shape. This value is used as 1.0D between adjacent structures and two other values of 0.0 and 0.5D can be assumed. Table 3 presents the considered SDs between RC MRFs and SMRFs.

Table 3 SDs between adjacent RC MRFs and SMRFs

2.4 Using VDs between structures

VD is a kind of energy dissipation device that transforms kinetic energy into heat energy to dissipate the seismic energy due to earthquakes. Equation (7) shows the relation between the VD force, FVD, the damping coefficient, C(α), the relative velocity, \(\dot{x}\), the signum function, sgn, and the damper velocity exponent, α [26,27,28,29,30,31,32,33,34,35,36,37,38,39].

$$F_{{{\text{FVD}}}} = C\left( \alpha \right)\left| {\dot{x}} \right|^{\alpha } {\text{sgn}} \left( {\dot{x}} \right)$$
(7)

The damper velocity exponent can take values from 0.0 to 1.0 for NVDs or LVDs, respectively. To calculate the supplemental damping ratio, ξVD, of VDs implemented between adjacent RC MRFs and SMRFs, modified equation introduced by Kandemir-Mazanoglu and Mazanoglu [30] was used:

$$\xi_{{{\text{VD}}}} = \frac{{\left( {\max \left\{ {T_{1,1} ,T_{1,2} } \right\}} \right)\mathop \sum \nolimits_{j} C\left( \alpha \right)_{j} \left( {\phi_{j,1} - \phi_{j,2} } \right)^{2} }}{{4\pi \mathop \sum \nolimits_{i} m_{i} \phi_{i}^{2} }}$$
(8)
$$C\left( \alpha \right) = \frac{{C\left( {\alpha = 1} \right)\left( {\min \left\{ {\omega_{1,1} ,\omega_{1,2} } \right\}X_{0} } \right)^{1 - \alpha } }}{\beta }$$
(9)
$$\beta = \frac{{2^{2 + \alpha } \Gamma^{2} \left( {1 + \frac{\alpha }{2}} \right)}}{{\pi \Gamma \left( {2 + \alpha } \right)}}$$
(10)

where T1,1, T1,2 are the fundamental period for the structures, the relative horizontal deformation corresponding to the first mode shape between floor levels of adjacent RC MRFs and SMRFs is obtained by \(\left( {\phi_{j,1} - \phi_{j,2} } \right)\). Moreover, X0 is the maximum relative displacement of the adjacent structures, ω1,1 and ω1,2 are the natural frequencies of the adjacent buildings, and Γ is the gamma function. To model VDs, it was considered that the VDs with rigid supporting do not reach their stroke limits during seismic excitations due to assumption of their large enough stroke limits.

In this research, both of NVDs or LVDs were considered between the aforementioned adjacent structures. Assuming three SDs, three ground motion data sets of Near-fault Pulse-Like (NPL), Near-fault No-Pulse (NNP), and Far-Fault (FF) seismic records suggested by FEMA-P695 [61] were used to find out the effects of earthquake events. Table 4 presents all the considered conditions (1086 models). In addition, all structures were analyzed in alone condition.

Table 4 Considered adjacent pounding RC MRFs and SMRFs for optimal placement of NVDs or LVDs

3 Results of analysis

3.1 Moment-rotation curve

Modified Ibarra–Krawinkler bilinear-hysteretic model (see [62,63,64]) was used to model the plastic hinges of structural elements. To compare the effects of pounding and implementing LVDs between the structures, the moment-rotation curves were used. Figures 6 and 7 present a comparison between beam and column hinges of the 3-story SMRF colliding with 5-story RC MRF in pounding situation and implementing LVDs between structures, respectively, subjected to NNP record (Northridge, 1/17/1994, Sepulveda VA Hospital station) assuming SD equal to 0.0 and Sa (T1) = 0.92 g. According to results, pounding can increase the maximum rotation of beam and column by 16% and 29.1% (for the beam from 0.042 to 0.050 rad, and for the column from 0.034 to 0.048 rad), respectively. In a structure, columns play a crucial role in the total collapse and the results show that 29.1% of column rotation will be added due to collisions. So it is important to find a solution to resist this sudden force. According to this result, adding VDs between the colliding structures is an alternative. The results confirm that using LVDs between structures can decrease the maximum values of the moment-rotation curves for beams and columns by 48% and 31.25% (for the beam from 0.050 to 0.026 rad, and the column from 0.048 to 0.033 rad), respectively. It is worth mentioning that this reduction can cause overall improvement in performance levels. Similar results were also observed for beams and column hinges of other colliding structures with different SDs and VDs.

Fig. 6
figure 6

Comparison between hinges of a beam, b column of 3rd floor of the 3-story SMRF colliding with 5-story RC MRF assuming SD of 0.0

Fig. 7
figure 7

Comparison between hinges of a beam, b column of 3rd floor of the 3-story SMRF colliding with 5-story RC MRF considering LVDs in all floor levels for SD of 0.0

3.2 IDA curves of pounding structures

To better investigate the effects of adding VDs on the seismic limit-state capacity of the colliding structures, the Incremental Dynamic Analysis (IDA) was used. Although many intensity measures were introduced by the researchers, Sa(T1) was selected for this purpose, and IDAs were performed assuming three ground motion sets of NPL, NNP, and FF suggested by FEMA-P695 [61]. OpenSees [49] software is an open-source developed program that can be used for accomplishing computational simulations in earthquake engineering to obtain the structural performances. The structural elements can be defined in interpreter (e.g. Python or Tcl) and different types of numerical solutions can be used for seismic analysis, which includes nonlinear time-history analysis or IDAs. It should be noted that new materials and structural elements have been added in this software to determine seismic behavior of members. To control, monitor and classify the output results, MATLAB [65] was used, which is a programming platform with wide range of capabilities. In real condition, it is possible that RC MRF and SMRF are constructed next to each other. Taking into account the pounding phenomenon, the adjacent structures may have different collapse states, in which, one of the structures may experience total failure before the next one. Therefore, it is important to consider the real condition of two colliding structures and take into account that one of the structures would collapse before the other one. To tackle this issue, the Tcl programing code, that uses MATLAB [65] and OpenSees [49] softwares simultaneously, was developed. This program allowed us to consider the effects of collapsed structure during the analysis, and this structure was not removed during further analysis until the total collapse of the second structure. In this way, the real condition of pounding phenomenon could be simulated. Using the program, both limit-state capacities of colliding structures can be obtained in one model that decreases the analysis time, and the effects of collapsed structure can be considered in the response of the second structure that can increase the accuracy of modeling. Figure 8 presents the IDA curves (black lines) and the median IDA curves (pink lines) (M-IDAs) of the 9-story RC MRFs (a) and the 9-story SMRFs (b) subjected to NPL records for SD of 1.0.

Fig. 8
figure 8

IDA curves for, a the 9-story RC MRFs, b the 9-story SMRFs assuming LVDs between all stories subjected to NPL records for SD of 1.0

3.3 Performance level of structures

Following recommendations of FEMA 356 [66], the allowable interstory drift for primary structural elements were assumed for performance levels of Immediate Occupancy (IO), Life Safety (LS), Collapse Prevention (CP), and total Collapse (C) according to defined damages.

The allowable values of interstory drift ratio of 1.0%, 2.0%, and 4.0%, were assumed for the performance of IO, LS, and CP for RC MRFs, respectively. In addition, for SMRFs, the allowable values of interstory drift ratio of 0.7%, 2.5%, and 5.0%, respectively, were considered. In both structures, the flat part of M-IDAs presents the total collapse of the structure (C). Table 5 shows the performance levels of RC MRFs and SMRFs in no pounding condition considering three record subsets. It can be seen that, in the case of RC MRFs, the values of M-IDAs for assumed performance levels in NNP subset are higher than for other subsets. It is also correct for the 3-story SMRF, while for in the 5-, and 9-story SMRFs, the assumed performance levels in FF subset are higher than for other subsets.

Table 5 Limited state capacities of the RC MRFs and SMRFs in alone condition assuming three record subsets

3.4 Comparing implementing NVDs or LVDs

Figure 9 compares the results of using NVDs or LVDs in the floor levels of all stories on M-IDAs of the 3-story SMRF colliding with 3-story RC MRF subjected to NPL for SD of 1.0D. According to Fig. 9, using LVDs between structures prone to pounding can increase M-IDAs of the RC MRFs by 33.06% (from 1.104 to 1.469), while decreasing M-IDAs of the SMRFs by 16.22% (from 1.892 to 1.585). The results confirm that using NVDs or LVDs has the same effect in M-IDAs that increases M-IDAs of RC MRFs and decreases M-IDAs of SMRFs. In other words, there is no difference between using NVDs or LVDs. These VDs can decrease M-IDAs of 3-story SMRF while increasing M-IDAs of 3-story RC MRF. The amount of M-IDAs in the aforementioned performance levels obtained from the analysis is presented in Table 6. According to this table, in each performance level, M-IDAs can show which kind of VDs have better performance. It can be seen that the LVDs added to all story levels have better performance levels, as compared to the NVDs.

Fig. 9
figure 9

Comparing the effects of the NVDs or LVDs implemented in all story levels on M-IDAs of a the 3-story SMRF, b the 3-story RC MRF including NPL record subset for SD of 1.0D

Table 6 Limited state capacities of the 3-story SMRF and the 3-story RC MRF structures with different VDs implemented in all story levels subjected to NPL record subsets for SD of 1.0D

Figure 10 compares the results of using NVDs or LVD in the second-floor level on M-IDAs of the 3-story SMRF colliding with 3-story RC MRF subjected to NPL for SD of 1.0D. It can be seen that the LVD added at the second-floor level increases M-IDAs of the 3-story RC MRF more than NVDs. In addition, LVD added at the second-floor level of the 3-story SMRF causes less reduction in M-IDAs, as compared to NVDs. LVD can also prevent further damages. To better compare the results, Table 7 presents the values of the performance levels of colliding structures in detail. It can be seen from the table that using LVD at the second level of colliding structures results in better performance levels increasing M-IDAs of the 3-story RC MRF by 15.67% (from 1.104 to 1.277) or decreasing M-IDAs of the 3-story SMRF by 7.02% (from 1.892 to 1.759). Therefore, according to this sensitivity analysis, the placement of LVDs between adjacent structures will be investigated due to their better performance, as compared to NVDs. It is worth noting that similar results were also observed for other record subsets.

Fig. 10
figure 10

Comparing the effects of the NVDs or LVDs implemented in 2nd story level on M-IDAs of a the 3-story SMRF, b the 3-story RC MRF including NPL record subset for SD of 1.0D

Table 7 Limited state capacities of the 3-story SMRF and the 3-story RC MRF assuming different VDs implemented in 2nd story level subjected to NPL record subsets for SD of 1.0D

3.5 Comparing M-IDAs of 3-story SMRF pounding with RC MRFs

Figure 11 presents the effects of using LVDs on M-IDAs of the 3-story SMRF and 3-story RC MRF subjected to NPL for SD of 1.0D. The models were defined according to Table 4. Using LVDs at all floor levels (3St-3RC-4) increases M-IDAs for the 3-story RC MRF by 32.48% (from 1.105 to 1.464) which is more than other assumed models considering LVD at the second-floor level (3St-3RC-1), at the third-floor level (3St-3RC-2), and at both first and third-floor level simultaneously (3St-3RC-3) by 12.4%, 13.4%, and 7.3%, respectively. Therefore, the best model to improve the performance levels of the 3-story RC MRF is implementing the LVDs according to the condition defined for 3St-3RC-4 in Table 4. The values of the four performance levels are presented in Table 8. On other side, for improving the performance levels of IO and LS for the 3-story SMRF, using the condition of 3St-3RC-2, and for the performance levels of CP and C, using the condition of 3St-3RC-3 can be a good alternative. Because these conditions, 3St-3RC-2 and 3St-3RC-3, can cause less reduction in M-IDAs, as compared to other models. Although using the 3St-3RC-4 is the best alternative for the 3-story RC MRF, this condition can cause the largest reduction in M-IDAs of the 3-story SMRF. Therefore, it is suggested to consider both structures' performance levels in retrofitting approach and choose the best model according to required performance levels.

Fig. 11
figure 11

Comparison M-IDAs of a the 3-story SMRF, b the 3-story RC MRF in pounding condition including NPL record subset for SD of 1.0D

Table 8 Limited state capacities of the 3-story SMRF and the 3-story RC MRF structures subjected to NPL record subsets for SD of 1.0D

Figure 12 presents the results of using LVDs on M-IDAs of the 3-story SMRF and 5-story RC MRF subjected to NPL for SD of 1.0D. Using LVD at the third-floor level (3St-5RC-2) increases M-IDAs for the 5-story RC MRF by 26.8% (from 0.987 to 1.252) which is more than other assumed models considering LVD at second-floor level (3St-5RC-1), at both first and third-floor level simultaneously (3St-5RC-3), and at all floor levels (3St-5RC-4) by 5.4%, 13.8%, and 12.4%, respectively. Therefore, the best model to improve the performance levels of the 5-story RC MRF is implementing the LVD according to the condition defined for 3St-3RC-2 in Table 4. In addition, for other performance levels, the values are presented in Table 9. For the 3-story SMRF, the 3St-5RC-1 condition is a better alternative in performance levels of IO and LS with improvements in M-IDAs values by 17% and 4.8%, respectively, while this can cause smaller reduction in the performance level of CP by 13.32%. For the performance level of C, the results confirm that the 3St-5RC-3 condition, with the reduction by 4.75%, is the best alternative among all models. Adding LVDs between the structures can cause an increase or decrease due to the assumed performance levels and the kind of implementation.

Fig. 12
figure 12

Comparison M-IDAs of a 3-story SMRF, b 5-story RC MRF in pounding condition including NPL record subset for SD of 1.0D

Table 9 Limited state capacities of the 3-story SMRF and 5-story RC MRF structures subjected to NPL record subsets for SD of 1.0D

Figure 13 presents the results of using LVDs on M-IDAs of the 3-story SMRF and the 9-story RC MRF subjected to NPL for SD of 1.0D. Using LVDs at all floor levels (3St-9RC-4) increases M-IDAs for the 9-story RC MRF in performance levels of IO, LS, and CP by 5.5%, 2.1%, and 12.7%, respectively, and for the performance level of C, the 3St-9RC-1 condition has the highest increase, i.e. by 27.03% (from 0.529 to 0.672). Therefore, the best model to enhance the performance levels of the 9-story RC MRF is 3St-9RC-4 and 3St-9RC-1 according to the condition defined in Table 4. It can also be seen that adding LVDs does not have a significant effect on M-IDAs of the 3-story SMRF. Although in previous models of pounding between the 3-story SMRF and 3-, and 5-story RC MRF, the M-IDAs of the 3-story SMRF significant reduction was obtained, pounding between the 3-story SMRF and the 9-story RC MRF has smaller effect on M-IDAs of the 3-story SMRF. Therefore, by increasing the height of the adjacent structure, M-IDAs of the 3-story SMRF will have fewer changes. Table 10 provides information on M-IDAs of the 3-story SMRF in detail. The results can also be used for retrofitting both adjacent structures. For example, if the 3St-9RC-4 condition is selected for retrofitting the 9-story RC MRF adjacent to the 3-story SMRF, it will have a significant influence on M-IDAs of the 9-story RC MRF according to the information presented in Table 10. On other side, it will increase M-IDAs of the 3-story SMRF in performance levels of IO and LS, while decreasing the values of performance levels of CP and C. In this condition in retrofitting, it is suggested to check and retrofit the adjacent structure for the performance levels of CP and C, while it can be neglected in conservative way for other performances. It is worth noting that similar results were also observed for other record subsets.

Fig. 13
figure 13

Comparison M-IDAs of a the 3-story SMRF, b the 9-story RC MRF in pounding condition including NPL record subset for SD of 1.0D

Table 10 Limited state capacities of the 3-story SMRF and the 9-story RC MRF subjected to NPL record subsets for SD of 1.0D

3.6 Comparing M-IDAs of 5-story SMRF pounding with RC MRFs

Figure 14 presents the results of using LVDs on M-IDAs of the 5-story SMRF and the 5-story RC MRF subjected to NPL for SD of 1.0D. Using LVDs at all floor levels (5St-5RC-4) increases M-IDAs for the 5-story RC MRF by 30.3% (from 0.987 to 1.286) which is more than for other assumed models considering LVD at the 5th floor level (5St-5RC-1), at both 2nd and 5th floor levels (5St-5RC-2), and at the 1st, 3rd and 5th floor levels (5St-5RC-3) by 15.5%, 23.6%, and 21.3%, respectively. Therefore, the condition of 5St-5RC-4 is the best alternative to implement LVDs between structures. Table 11 presents details of M-IDAs of colliding structures in all performance levels. For the 5-story SMRF, the condition of 5St-5RC-1 is a better alternative due to the fact that it increases M-IDAs of the 5-story SMRF in IO and LS by 19.2% and 12.2%, respectively, while it decreases the values of CP and C by 1.5% and 0.39%, respectively. It can be seen that the reduction values of performance levels of CP and C do not significantly influence M-IDAs of the 5-story SMRF. For retrofitting purposes, using condition of 5St-5RC-4 can be the best suggestion for the 5-story RC MRF due to its increasing effects in all performance levels, but it should be said that this condition has a reduction effect on the CP and C performances of the 5-story SMRF. Therefore, it is suggested to check and retrofit the adjacent structure for the CP and C performances.

Fig. 14
figure 14

Comparison M-IDAs of a the 5-story SMRF, b the 5-story RC MRF in pounding condition including NPL record subset for SD of 1.0D

Table 11 Limited state capacities of the 5-story SMRF and the 5-story RC MRF subjected to NPL record subsets for SD of 1.0D

Figure 15 presents the results of using LVDs on M-IDAs of the 5-story SMRF and the 5-story RC MRF subjected to NNP for SD of 0.0. Using LVDs in all floor levels (5St-5RC-4) increases M-IDAs for the 5-story RC MRF by 59.6% (from 0.987 to 1.575) which is more than for other assumed models considering LVD at the 5th floor level (5St-5RC-1), at both 2nd and 5th floor levels (5St-5RC-2), and at the 1st, 3rd and 5th floor levels (5St-5RC-3) by 40.4%, 48.3%, and 48.3%, respectively. It can be noted that by decreasing the SD from 1.0 to 0.0, the performance of LVDs implemented at all floor levels (5St-5RC-4) between the 5-story SMRF and the 5-story RC MRF increases by 37.71% (from 23.25% for SD of 1.0 to 37.33% for SD of 0.0). Therefore, this strategy is more useful to retrofit the 5-story RC MRF in any adjacency condition. Table 12 presents details of M-IDAs of colliding structures in all performance levels.

Fig. 15
figure 15

Comparison M-IDAs of a the 5-story SMRF, b the 5-story RC MRF in pounding condition including NNP record subset for SD of 0.0

Table 12 Limited state capacities of the 5-story SMRF and the 5-story RC MRF subjected to NNP record subsets for SD of 0.0D

For the 5-story SMRF, the condition of 5St-5RC-3 is a better alternative due to the increased M-IDAs of the 5-story SMRF in performance levels of IO, LS, and CP by 5.9%, 13.2%, and 1.86%, respectively, while it decreases the value of performance level of C by 0.39%. According to retrofitting criteria (Seismic Evaluation and Retrofit of Existing Buildings), there were some retrofitting purposes that the designer regarding the knowledge about the structure can choose for a building to check them. Most of the purposes of retrofitting are directed to achieve the performance levels of IO and LS. Therefore, in these performance levels, the designer should consider both structures' performances to assure choosing the best alternative in implementing the LVDs between the structures. In addition, the designer can choose the condition of 5St-5RC-1 regarding the details presented in Table 12. In this condition, although the performance levels of the 5-story SMRF were more or less unchanged (fluctuating between + 4.02% and − 0.47%), the performance levels of IO, LS, CP, and C for the 5-story RC MRF increased by 6.4%, 15.6%, 32.4%, and 40.4%, respectively.

Figure 16 presents the results of using LVDs on M-IDAs of the 5-story SMRF and the 9-story RC MRF subjected to NPL for SD of 1.0D. Using LVDs at both 2nd and 5th floor levels (5St-9RC-2) can be a good alternative for the 9-story RC MRF that causes a reduction in performance levels of IO and LS by 4.3% and 6.6%, respectively, while increasing the performance levels of CP and C by 2.39% and 23.3%, respectively. Other conditions of considering LVD at 5th floor level (5St-9RC-1), at the 1st, 3rd, and 5th floor levels (5St-9RC-3), and at all floor levels (5St-9RC-4) increase M-IDAs for the 9-story RC MRF by 6.8%, 11.9%, and 12.9%, respectively. Table 13 presents details of M-IDAs of colliding structures in all performance levels.

Fig. 16
figure 16

Comparison M-IDAs of a the 5-story SMRF, b the 9-story RC MRF in pounding condition including NPL record subset for SD of 1.0D

Table 13 Limited state capacities of the 5-story SMRF and 9-story RC MRF subjected to NPL record subsets for SD of 1.0D

For the 5-story SMRF, the conditions of 5St-9RC-3 and 5St-9RC-4 are better alternatives due to increasing M-IDAs of the 5-story SMRF in performance levels of IO and LS by 30.1% and 10.2%, respectively. While for other performance levels, the conditions of 5St-9RC-1 can be chosen that decrease the values of the performance level of CP and C by 6.8% and 5.59%, respectively, less than for other conditions. Table 13 presents useful information concerning retrofitting these two adjacent structures. For example, the designer can decide to choose one of the conditions to implement the LVDs between the structures relying on the details provided in Table 13 and checking the effects of retrofitting one structure (e.g. the 5-story SMRF) on the other one (e.g. the 9-story RC MRF).

3.7 Comparing M-IDAs of 9-story SMRF pounding with RC MRFs

Figure 17 presents the results of using LVDs on M-IDAs of the 9-story SMRF and the 3-story RC MRF subjected to NPL for SD of 0.0. Using LVDs at all floor levels (9St-3RC-4) increases M-IDAs for the 3-story RC MRF in performance levels of IO, LS, CP, and C by 11.2%, 18%, 42.5%, and 32.8%, respectively. Moreover, other conditions of considering LVD at the 2nd floor level (9St-3RC-1), at the 3rd floor level (9St-3RC-2), and at the 1st and 3rd floor levels (9St-3RC-3) increase M-IDAs for the 3-story RC MRF by 16.7%, 19.9%, and 7.3%, respectively. Table 14 presents details of M-IDAs of colliding structures in all performance levels. For the 9-story SMRF, the conditions of 9St-3RC-3 and 9St-3RC-1 are better alternatives due to increasing M-IDAs of the 9-story SMRF in performance levels of IO and LS by 30.4% and 8%, respectively, and increasing the performance levels of CP and C by 21.1% and 36%, respectively. Although using the condition of (9St-3RC-4) is the best alternative for the 3-story RC MRF, this condition also stands in the second rate for the 9-story SMRF. Therefore, according to Table 14, for retrofitting purposes, the designer can decide to choose one of the conditions to implement the LVDs between the structures.

Fig. 17
figure 17

Comparison M-IDAs of a the 9-story SMRF, b the 3-story RC MRF in pounding condition including NPL record subset for SD of 0.0

Table 14 Limited state capacities of the 9-story SMRF and 3-story RC MRF subjected to NPL record subsets for SD of 0.0D

Figure 18 presents the results of using LVDs on M-IDAs of the 9-story SMRF and the 9-story RC MRF subjected to NPL for SD of 1.0D. Implementing LVDs at the floor levels of the 1st, 3rd, 5th, 7th, and 9th (9St-9RC-7) increases M-IDAs for the 9-story RC MRF in performance levels of IO, LS, and CP by 2.4%, 2.9%, and 9.9%, respectively. While for the performance level of C, the condition of 9St-9RC-8 increases M-IDAs for the 9-story RC MRF by 19.3%, which is more than for other conditions. Table 15 presents details of M-IDAs of colliding structures in all performance levels.

Fig. 18
figure 18

Comparison M-IDAs of a the 9-story SMRF, b the 9-story RC MRF in pounding condition including NPL record subset for SD of 1.0D

Table 15 Limited state capacities of the 9-story SMRF and 9-story RC MRF structures subjected to NPL record subsets for SD of 1.0D

For the 9-story SMRF, all the conditions increase the amount of M-IDAs and they can be chosen for retrofitting purposes. The conditions of 9St-9RC-1, 9St-9RC-4, 9St-9RC-6, and 9St-9RC-8 are good alternatives to increase the performance level of IO by 66.1%. The only difference between them is the cost of implementation of LVDs. In the condition of 9St-9RC-1, only one LVD at the top floor can increase M-IDAs of the 9-story SMRF in the performance level of IO by the same value as in the case of other conditions (e.g. 9St-9RC-4, 9St-9RC-6, and 9St-9RC-8) with a lower cost of the implementation. In addition, the condition of 9St-9RC-1 is the best alternative for increasing the performance levels of LS and CP by 31% and 26%, respectively. Moreover, the condition of 9St-9RC-6 increases the performance level of C by 21.5%. It can be noted that using Table 15 can help designers to choose and compare the alternatives of adding LVDs between the structures by considering the amount of increased values of performance levels and the cost of the implementation. Also, it is suggested that the performance levels of the adjacent structure should be checked based on the influence of adding LVDs that were presented in the figures.

4 Seismic failure probability

To evaluate the effects of implemented VDs, the seismic fragility curves were plotted for the performance level of C. Figure 19 illustrates the seismic fragility curves of the 3-story SMRF and RC MRF with different types of VDs implemented on second story level including NNP records given SD of 1.0D. The Sa(T1) corresponding to the failure probability of 50% for the 3-story SMRF in the performance level of C assuming VDs with damper velocity exponent of 0.3, 0.7, and 1.0 were determined by 1.61, 1.71, and 1.79, respectively, in which, the LVDs achieved higher values of Sa(T1) that shows the lower value of the failure probability. On the other side, the Sa(T1) corresponding to the failure probability of 50% for the 3-story RC MRF in the performance level of C assuming VDs with damper velocity exponent of 0.3, 0.7, and 1.0 were determined by 1.27, 1.29, and 1.35, respectively. The results confirmed that the structures with implemented LVDs achieved higher values of Sa(T1) in the failure probability of 50%.

Fig. 19
figure 19

Seismic fragility curves of a the 3-story SMRF, b the 3-story RC MRF assuming implemented NVDs or LVDs in second story level including NNP record subset for SD of 1.0D

Figures 20 and 21 illustrate the seismic fragility curves of the 3-story and 5-story SMRFs colliding with RC MRFs of similar height assuming different types of implementing VDs including NNP and NPL records and SD of 1.0D, respectively. It is obvious that adding LVDs can significantly decrease the seismic failure probability of RC MRFs, while it can increase the seismic failure probability of SMRFs. Therefore, it can be concluded that different types of lateral resisting systems can affect the results of implementing VDs between the adjacent structures with similar heights. In addition, implementing VDs in all story levels can be the best alternative for retrofitting the RC MRFs, while this condition can significantly increase the seismic failure probability of SMRFs. Thus, it is recommended that the condition of adjacent structure should be considered in the retrofitting process.

Fig. 20
figure 20

Seismic fragility curves of a the 3-story SMRF, b the 3-story RC MRF in pounding condition including NNP record subset for SD of 1.0D

Fig. 21
figure 21

Seismic fragility curves of a the 5-story SMRF, b the 5-story RC MRF in pounding condition including NPL record subset for SD of 1.0D

Figures 22 and 23 illustrate the fragility curves of the 3-story SMRF and 5-story RC MRF, and the 5-story SMRF and 9-story RC MRF including NNP records and SD of 1.0D, respectively. It is presented that implementing VDs can increase the failure probability of shorter structures (i.e. the 3-, and 5-story SMRFs), while the failure probability of taller structure remains more or less unchanged, except for placement of condition two (see Table 4). In the case of pounding between taller and shorter structures, results of failure probability for the 9-story SMRF and 3-story RC MRF, including NNP records for SD of 0.0, were compared in Fig. 24. It can be observed from the figure that implementing VDs in this condition can help both structures and improve their failure probabilities. It can be said that, due to possibility of collapse in the middle of the 9-story SMRF, implementing the VD in the top floor of the 3-story RC MRF prevents the failure of the 9-story SMRF; then, as a result, the failure probability is reduced. On the other hand, this situation helped the 3-story RC MRF to decrease the failure probability.

Fig. 22
figure 22

Seismic fragility curves of a the 3-story SMRF, b the 5-story RC MRF in pounding condition including NNP record subset for SD of 1.0D

Fig. 23
figure 23

Seismic fragility curves of a the 5-story SMRF, b the 9-story RC MRF in pounding condition including NNP record subset for SD of 1.0D

Fig. 24
figure 24

Seismic fragility curves of a the 9-story SMRF, b the 3-story RC MRF in pounding condition including NNP record subset for SD of 0.0

5 Retrofitting modification factors

Based on the results concerning the M-IDAs of colliding structures, Retrofitting Modification Factors (RMFs) were calculated after dividing the M-IDAs of the colliding structures in the retrofitted condition (presented in Table 4) by the corresponding values of M-IDAs without any retrofitting devices (e.g. VDs). The RMFs can be applied to the structures with the same conditions and structural elements to help designers approximately calculate the performance levels of the colliding structures when using LVDs. RMFs can be used for all kinds of assumed structures and aforementioned SDs. According to the results for different record subsets, the difference between the performance levels of M-IDAs for the colliding structures with and without retrofitting devices are approximately equal. Therefore, RMFs can be successfully used for colliding structures subjected to three aforementioned record subsets. In addition, RMFs can help designers to estimate the amount of M-IDAs after retrofitting. To calculate RMFs, the pounding model and the condition of retrofitting according to the Table 4 should be firstly selected. Then the values obtained from Tables 16, 17, 18, 19, 20, 21, 22, 23 and 24 can be applied to the pounding condition of models. For example, for the condition of 9St-3RC-3 for SD of 1.0D, M-IDAs of the 9-story SMRF and 3-story RC MRF colliding structures should be multiplied by 1.035 and 1.073 (RMFs according to Table 22), respectively, to achieve the performance level of C of the retrofitted structures.

Table 16 RMF of the 3-story SMRF and the 3-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D
Table 17 RMF of the 3-story SMRF and the 5-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D
Table 18 RMF of the 3-story SMRF and the 9-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D
Table 19 RMF of the 5-story SMRF and the 3-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D
Table 20 RMF of the 5-story SMRF and the 5-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D
Table 21 RMF of the 5-story SMRF and the 9-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D
Table 22 RMF of the 9-story SMRF and the 3-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D
Table 23 RMF of the 9-story SMRF and the 5-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D
Table 24 RMF of the 9-story SMRF and the 9-story RC MRF subjected to all record subsets for SD of 0.0 and 1.0D

6 Conclusions

This study has been focused on seismic limit-states of SMRFs and RC MRFs prone to earthquake-induced pounding. The effects of adding VDs between adjacent structures have been carried out and proper RMFs for retrofitting purposes have been determined assuming three SDs of 0.0, 0.5D, and 1.0D. In this study, a Tcl code was developed to assess the limit-state capacity of adjacent pounding structures taking into account the collapsed structure. The results are summarized as follows:

  • The results confirm that pounding between adjacent structures can cause an increase in the maximum values of the moment-rotation curves of beams and columns (e.g. beam and column of the 3-story SMRF colliding with 5-story RC MRF experienced an increase by 16% and 29.1%, respectively). The placement of LVDs between structures can be effective to reduce the values of the moment-rotation curves for beams and columns by 48% and 31.25%, respectively.

  • Regarding RC MRFs and SMRFs without any adjacent structure, the values of M-IDAs for the IO, LS, CP, and C performance levels of RC MRFs including the NNP records were higher than for other subsets. While this was correct for the 3-story SMRF, in the case of 5-, and 9-story SMRFs, the assumed performance levels in the FF subset were higher than for other subsets.

  • Comparing the results of using NVDs and LVDs, it can be seen that LVDs attain better performance levels, as compared to the NVDs, for three different record subsets and SDs.

  • The results confirm that implementing LVDs between adjacent structures play a crucial role in increasing the performance levels of RC MRFs. For example, in the condition of 3St-3RC-4, M-IDAs for the 3-story RC MRF increased by 32.48%, in the condition of 3St-5RC-2, M-IDAs for the 5-story RC MRF increased by 26.8%, in the condition of 3St-9RC-1, M-IDAs for the 9-story RC MRF increased by 27.03%. Although RC MRFs achieved higher performance levels, the alternative conditions were caused by the reduction in M-IDAs of the 3-story SMRF. Therefore, it is suggested to consider both structures' performance levels in retrofitting approach and choose the best model according to required performance levels.

  • RMFs were proposed to approximately predict the M-IDAs of the structures after retrofitting. The RMFs can be easily applied to the structures with the same structural elements to help designers approximately calculate the performance levels of the colliding structures when using LVDs between the structures without involving analytical difficulties.

  • Comparing pounding between MRFs of similar height (i.e. the 3-, and 5-story) shows that adding VDs can significantly decrease the seismic failure probability of RC MRFs, while it can increase the seismic failure probability of SMRFs. The results confirm that implementing VDs can increase the failure probability of shorter structures (i.e. the 3-, and 5-story SMRFs), while the failure probability of taller structure remains more or less unchanged, except for placement of condition two. Comparing pounding between taller SMRF and shorter RC MRF shows that implementing the VD at the top of the shorter RC MRF prevents the failure of the taller SMRF; then, as a result, the failure probability is reduced.

  • To address the reason behind this, it can be said that pounding phenomenon leads to complex situation that any changes, such as lateral resisting system, total weight of structure, fundamental period, and implementing VDs, can affect the impact forces at the floor levels, which may change the seismic behavior of both structures. Therefore, it is recommended that the condition of adjacent structure should be considered in the retrofitting process of the building under investigation.