Abstract
Heat treatment is often required for ultra-high-performance concrete (UHPC) to achieve high strength. To broad its use in construction, the effect of different curing conditions on the properties of UHPC has been developed for many years. The experimental investigation of large scale ultra-high-performance fibre reinforced concrete (UHPFRC) beams is limited. In the present study, UHPFRC specimens and concrete cured at 20 °C were prepared to investigate the properties and flexural behaviour. The standard cubic compressive strength of UHPFRC specimens cannot be achieved at curing temperature of 20 °C. The bearing capacity under flexure was enhanced with the increase of reinforcement ratio. The failure modes of beams changed from ductile to brittle as the reinforcement ratio increased from 1.26 to 9.50%. The flexural behaviour of UHPFRC beams cured at room temperature was in accordance with the UHPFRC beams cured at high temperature in previous studies. In addition, the calculation model of CECS38-2004 underestimated the bending moment capacity of the under-reinforced UHPFRC beams (with reinforcement ratio from 0 to 7.85%) and overestimated the bending moment capacity of the UHPFRC beams with high reinforcement ration of 9.50%.
Similar content being viewed by others
Introduction
Ultra-high performance fibre reinforced concrete (UHPFRC) is a form of concrete with a ultra-high compressive strength (150 to 200 MPa), a high tensile strength (> 7 MPa), a high bending strength and a low water-cement ratio of 0.2 or less1. It has been an attractive choice for high buildings and long span bridges due to its superior mechanical performance. The raw materials of UHPFRC consist of cement, fine sand, silica fume, quartz powder, superplasticizer, fibres and the mineral additives with different binding characteristics2,3. Many studies have been performed to investigate the properties and mechanical behaviour of UHPFRC. The mechanical behaviour and strength of UHPFRC depend on the quality of raw materials, the mix proportion and the curing regimes. The effect of mixture ratios on the strength of UHPFRC has been examined at a wide range. The water-binder and water-cement ratios maintained at approximately 0.16 to 0.20 in UHPFRC4,5. The compressive strength of UHPFRC increased with the decrease of the ratio of water to cement because of the enhancing interface area of aggregate-matrix and fibre-matrix5. The high range of water reducer was employed to retain the workability of UHPFRC with low water-cement ratio6,7.
The concrete could obtain excellent mechanical properties by adding fibres. The fibres in UHPFRC supplied a crack control and resistance to the pull-out force for the cement matrix after failure5. Thus, a number of research focus on the effects of fibre including the geometry8, length9,10 and volume fractions11, the orientation12,13 and the type14. With a constant cross-sectional area, the triangular and square-shape fibres were more efficient in improving the mechanical bond than the circular-shaped15. Moreover, the UHPFRCs with the twisted addition of hooked at end steel fibres had a greater tensile strength than those with short straight-line fiber of steel16. The flexural resistance, deflection ability and robustness of UHPFRC were improved by increasing the fibre length10. However, the UHPFRC with shorter fibres had greater workability5. Moreover, for a constant fibre volume fraction, the shorter the length of the fibre, the greater the amount of fibres on the crack area, which affecting the tensile behaviour of the UHPFRC.
The properties of UHPFRC also depend on the curing conditions17. Autoclaving at a moderate temperature of 65 °C and cured at around 85 to 90 °C are employed in UHPFRC. The UHPFRC showed higher compressive strength after steam and autoclave curing at 90 °C than that under room temperature curing18,19,20. The improvement in the compressive strength under high temperature is due to the accelerated hydration of cementitious material and the secondary hydration between mineral admixtures and calcium hydroxide21. Moreover, higher curing temperature showed positive effect on the modulus of elasticity of UHPC due to enhanced hydration of cementitious materials22. The flexural strength of UHPFRC produced with ground granulated blast-furnace slag (GGBS) was significantly improved under higher temperature curing. The increase in flexural strength can be attributed to bonds between matrix and aggregate which are improved by the increasing rate of reaction of binder and CSH chain length under high temperature curing19. Moreover, the porosity and density of UHPFRC can be reduced when the specimens were cured at high temperature due to expansion of CSH gel3.
However, the high temperature and long duration curing for UHPFRC limit its broader application due to the high energy consumption and manufacturing price and the low production efficiency. Developing UHPFRC without heat treatment would promote the widespread use of the product. Thus, many extensive studies of UHPFRC cured at room temperature have been carried out18,19,23,24,25,26. Table 1 summarizes the test results of previous studies of the UHPFRC cured at room temperature. These studies investigated and acquired the mechanical properties of the UHPFRC such as the compressive strength and tensile strength. However, the flexural behaviour of large scale UHPFRC beams have not been studied in these studies. A number of research have investigated the effect of raw materials, mix proportion, fibres and curing conditions on the flexural behaviour of large scale UHPFRC beams27,28,29,30,31,32,33. To the best of authors’ knowledge, the investigation of flexural behaviour of UHPFRC beams cured at room temperature is limit. Some research studies have demonstrated the flexural behaviour of UHPFRC beams cured at room temperature27,33 but only a small range of reinforcement ratio was employed. Importantly, the load carrying capacity, failure modes, and ductility depend on the reinforcement ratio of concrete beams to some extent34,35. Concrete beams could obtain higher loading capacity with an increase reinforcement ratio34 while higher ductility (ductile failure) had been observed in low reinforcement ratio35. Thus, comprehensive understanding of the mechanical behaviour and properties of UHPFRCs with different reinforcement ratios cured at room temperature are still required.
The aim of this paper is to examine the flexural behaviour of the UHPFRC beams with a wide range of reinforcement ratio from 0 to 9.5% cured at room temperature. The investigated behaviours included crack patterns, failure mode, flexural behaviour, and ductility. Basic mechanical properties such as compressive strength, tensile strength and flexural strength of UHPFRC specimens were determined prior to the investigation of UHPFRC beams. Experimental results of the UHPFRC beams were compared to the theoretical prediction by the Chinese standards to evaluate the applicability of these standards in UHPFRC cured at room temperature. Following Codes were used in this study: “Technical specification for fibre reinforced concrete structures” CECS38-200438, “Standard for test method of mechanical properties on ordinary concrete” GB/T 50081-201939, “Technical Specification for Reactive Powder Concrete Structures” DBJ43T325-201740.
Experimental program
Experimental program involved characterizing the material properties and determining the parameters of the calculation model and included studying the flexural behaviour of UHPFRC beams.
Materials and mixture proportion
An ultra-high-performance fibre-reinforced cementitious composite was prepared in this study. The range of mixture ratios to acquire excellent UHPFRC were examined and summarized by many research studies. In order to manufacture UHPFRC specimens with high quality, the mixture proportions were chosen from the tests database5. Preferably, the water-cement ratio maintained at 0.16 to 0.20. The silica fume and silica flour of 10% to 30% of the cement mass were required to fill the voids between cement particles. The proportions of aggregate and superplasticizer were 110% and 2% of the cement mass, respectively. Moreover, the steel fibres content was recommended as a volume fraction of 2% to 3% based on the workability and mechanical performance of UHPFRC. The mixture proportions used in this study are summarized in Table 2. The cement used in this study was Ordinary Portland cement 42.5R. Silica sand with diameter of 360 to 600 μm and 600 to 840 μm was used as aggregates. Silica fume including 94% SiO2 with a diameter of 0.1 μm and silica flour with a diameter of 50 μm were added as fillers. The Dramix steel fibres were added at 2% by volume of the entire mix. As shown in Fig. 1, the steel fibres had 13 mm length and 0.2 mm diameter with a yield strength of 2850 MPa as reported by the manufacturer.
UHPFRC mix design
The mixing procedure consisted of mixing the cement, silica fume, silica flour and sand in dry state for 2 min. Then, the water mixed with superplasticizer was added into the dry mixture and mixed for 6 min. When the mixture became visibly flowable, the steel fibres were added and mixed for further 5 min.
Specimens and test methods
Compressive, tensile and flexural strength tests
A series compression and tension tests were conducted to characterize the material properties. To identify the compressive strength, specimens with dimensions of 100 × 100 × 100 mm3 and 100 × 100 × 300 mm3 were casted and tested. Dog-bone shaped specimens with a rectangular cross section of 50 mm × 100 mm and length of 368 mm were fabricated and tested for axial tensile strength as shown in Fig. 2. Specimens with dimension of 100 × 100 × 400 mm3 were tested for flexural tensile strength. All test specimens were reinforced with steel fibres but without rebars. These specimens were covered with plastic sheets immediately after casting and demoulded after 24 h. To identify the effect of curing temperature on the properties of UHPFRC, specimens with dimension of 100 × 100 × 100 mm3 were cured at three conditions including room temperature of 20 °C ± 0.5 °C and steam curing at 60 °C ± 0.5 °C and 90 °C ± 0.5 °C for 48 h after demoulded. Specimens were then cured in a fog room at room temperature for 28 days and then tested. Specimens with dimensions of 100 × 100 × 300 mm3 and 100 × 100 × 400 mm3 were cured in a fog room at room temperature for 28 days after demoulded and then tested. The compressive strength, tensile strength and flexural strength for each group were determined with three specimens.
Large scale beam specimens
Six groups of beams with different reinforcement ratios were fabricated and tested in this study as shown in Fig. 3. Each group consisted of three specimens. Control beams without any reinforcement were labelled as NR. For reinforced beams, rebars at the top were kept same i.e., single layer of two bars with 8 mm diameter. The beams were designated according to the arrangement of bottom reinforcement rebars. Beams with one rebar layer at the bottom with two 12 mm rebars were labelled as R12-1. R18-1 had one rebar layer at the bottom with two bars of 18 mm diameter. R18-2 had two layers of reinforcement at the bottom with two rebars of 18 mm in each layer while R20-2 had two reinforcement layers at the bottom containing two rebars of 20 mm per layer. R22-2 had two layers of rebars with two bars of 22 mm in each layer. All beams had the similar dimensions with an effective span length of 1600 mm and cross-section of 100 mm × 200 mm. To prevent any premature shear failure of the beam, shear reinforcement was provided. The shear reinforcement consisted of stirrups of 8 mm diameter spaced at 100 mm centre to centre throughout the beam.
The beams were fabricated one at a time because of the concrete mixer of 1000 L capacity and the larger quantity of mixtures required. The beams were fabricated by placing the concrete using back and forth placement method along the span of the beam. The specimens were covered with wet hessian and plastic sheets immediately after concrete casting and cured at room temperature for the first 24 h, prior to demolding. After demolding, the specimens were cured in a fog room at room temperature of 20 °C ± 0.5 °C for 28 days.
Test setup
Compressive, tensile and flexural strength tests setup
The compressive strength and flexural strength of the steel fibre-reinforced concrete were determined based on GB50081-2019. Specimens with dimension of 100 × 100 × 100 mm3 and 100 × 100 × 300 mm3 were used to determine the compressive strength by uniaxial compressive load applied at rate of 0.8 to 1.0 MPa/s. For the specimens with dimension of 100 × 100 × 300 mm3, the electrical strain gauges of 80.1 mm length were attached at the mid height to record the axial and lateral strains as show in Fig. 4a. Additionally, a dial gauge was used to measure the platen-to-platen displacement to measure the strains of the whole specimen to determine the elastic modulus.
To determine the tensile strength, as shown in Fig. 4b, the dog-bone shaped specimens with a rectangular cross section of 50 mm × 100 mm and length of 368 mm were loaded at rate of 0.05 mm/min according to41. The strain of specimens was measured by digital image correlation (DIC). DIC is a reliable non-destructive method based on speckle tracking and is used to analyse the full displacement field on the surface of specimens by digital images42,43,44.
To determine the flexural strength, specimens with a dimension of 100 × 100 × 400 mm3 were loaded at rate of 0.08 to 0.1 MPa/s according to GB50081-2019. Three electrical strain gauges with a length of 80.1 mm were glued on the side surface of the specimen at midspan at different heights to measure the strain as shown in Fig. 4c.
Large scale beam test setup
The beams were subjected to two equally concentrated loads applied at 267 mm from the mid span via four-point loading method according to GB/T50081-2019. Figure 5 shows the loading configuration details of concrete beams. The beam was set up on a steel frame with a capacity of 1000 kN. A single hydraulically actuated jack was used to supply the monotonically increasing load. Load was supplied through displacement control method at the rate of 10 mm/min. As shown in Fig. 5, LVDTs and electrical resistance strain gauges were used to measure the deflections and strains of the beams. Five gauges with a length of 80.1 mm were glued on the side surface of the beam at midspan at different heights and two gauges were located on the bottom surface of the beam at midspan. In addition, electrical strain gauges with length of 1 mm were glued to the steel rebar at midspan before the casting of the beam to measure the strains of steel.
Results and discussion
Properties of the UHPFRC specimens
Table 3 shows the test results of the UHPFRC specimens. It can be seen that the average cubic compressive strength increases from 102.90 to 156.46 MPa with the increase of curing temperature from 20 to 90 °C, which is consistent to the aforementioned literatures. The strength level of cubic compressive strength of UHPFRC was achieved for specimens cured at 90 °C, indicating that the mixture proportion and manufacturing method employed in this study can satisfy the strength requirement of normal UHPFRC5. The compressive strength of specimen with dimension of 100 × 100 × 300 mm3 was 79.08 MPa which was lower than the cubic compressive strength. It is stated that larger specimens released more stored energy than smaller specimens5.
The specimens with dimension of 100 × 100 × 400 mm3 were tested under four-point loading and the flexural strength was 17.7 MPa. The flexural strength of the specimens under four-point loading was calculated by Eq. (1) according to GB50081-2019 as follow:
where F is the applied load at failure, l is the length of span measured bearing to bearing, b is the width of cross-section and h is the depth of cross-section.
The axial tensile strength acquired from the dog-bone shaped specimen was 8.38 MPa.
Test results for beams
Crack pattern and failure mode
For all the beams, the load increased linearly until the formation of first crack. The presence of the first cracks was audibly indicated followed by the first visible micro-cracks at the bottom surface of the beams between the loading points. The number of micro-cracks increased with the increase of the load, and new cracks propagated toward the upper face. One or two cracks in the middle portion of the beam became significantly visible whereas other cracks did not show any visible increase in width. In addition, the compression zone of concrete moved toward to the top as the cracks developing. As the test progressing, a noticeable increase in the number of cracks occurred and the steel fibres began to pull out. Given that steel fibres carried the tensile load and resisted the opening of the crack, the width of the cracks increased more rapidly with slight increase in load after the steel fibres began to pull out. The tensile load on the other nearby fibres increased, leading to pulling out of even more steel fibres. As shown in Fig. 6, the increase of reinforcement ratio increased the number of cracks and reduced the width of cracks.
Three to five visible cracks were observed for NR group beams between the loading points. The cracks of NR group beams propagated to the depth of 0.5 h (height of the beam) at failure. All R group beams exhibited vertical cracks. In addition to vertical cracks, the number of diagonal cracks in the region between the loading point and the support increased with the increase of reinforcement ratio. One or two major cracks were formed during failure and then developed rapidly in length and width. Moreover, the depth of the crack increased with the increase of reinforcement ratio from 1.26 to 7.85%. At the end of the tests, the depths of crack for R12-1, R18-1, and R18-2 were about 0.60 h, 0.70 h, and 0.75 h, respectively. The depths of the crack for R20-2 and R22-2 were about 0.85 h and 0.7 h, respectively.
Concrete is known as a brittle material and shows immediate loss of load carrying capacity without reinforcement at failure45. Brittle failure was observed in NR beams as the ordinary concrete. The failure modes of R group beams were different from those of NR group beams, depending on the longitudinal reinforcement ratio. In terms of reinforcement ratio, the beams can be divided in to three groups: under-reinforced beams, balanced-reinforced beams and over-reinforced beams. Failure of under-reinforced beams was gradual and was accompanied by fairly large deflection. The ultimate load capacity of the beams increased with an increase in tensile reinforcement ratio but the deflection ductility decreased, leading to brittle failure34. Thus, failure of over-reinforced beams was more abrupt. The balanced-reinforced beams behaved in an intermediate manner between those of under-reinforced and over-reinforced beams. Moreover, ductile failure was always observed in under-reinforced beams while brittle failure was observed in over-reinforced beams. The balanced-reinforced beams appeared to fail in a fairly brittle manner35. Ductile failure occurred in under-reinforced beams because the steel yields and the concrete crushes simultaneously, causing considerable deformation34. With an increase of reinforcement ratio, the loading capacity of beams increases and the load distribution on each steel decreases. The concrete was crushed without prior yielding of the steel (less deformation), leading to a rapid propagation of cracks and sudden failure of concrete beams35. Ductile failure was observed for the beams R12-1, R18-1 and R18-2 with large deflection. As shown in Fig. 6b, c, d, the compression zone of the concrete crushing is small at failure. Thus, the reinforcement yielded before the beams reach the ultimate limit state in flexure. The yielding of reinforcement produced a ductile failure for these beams because the tensile reinforcement ratios of these beams were under-reinforced27. As shown in Fig. 6e, f, brittle failure was observed for the beams R20-2 and R22-2, accompanying with large concrete crushing of compression zone. The brittle failure indicated that the beams R20-2 and R22-2 could be balanced-reinforced or over-reinforced beams.
Load–deflection relationship
The failure loads and deflections of the tested beams are summarized in Table 4. It is clear to see that the flexural capacity of UHPFRC beams increased as reinforcement ratio increased. This trend is similar to other investigation27,29,32,46.
The deflection was measured at the mid span of the beam. Figure 7 shows the load–deflection relationship of the tested beams. Three distinct regions of the load–deflection relation can be observed in the NR group beams, including the linear zone before first cracking, yield stage, and rupture stage. The yield stage began when first cracking occurred and ended before reaching the maximum load. The rupture stage corresponded to that of strength losing. It can be seen that initial response of NR group beams was similar up to the peak load and then ruptured. The exact occurrence of the first crack was difficult to observe visually due to the multiple-cracking property of the UHPFRC. Thus, the crack load in this paper was defined as the load at the end of the initial linear stage in the load–deflection curve. The average peak load for the NR group beams was 40 kN and the average deflection measured for this load was 2.32 mm. After the peak was achieved, the specimens underwent into a softening stage, which showed a brittle failure pattern.
The beams R12-1, R18-1 and R18-2 showed similar trend in load–deflection behaviour. The deflection increased linearly and was proportional to the load until reaching the peak value of the load. After the peak value was achieved, the deflection increased while the load kept constant, showing a ductile failure pattern.
The load–deflection behaviour of the beams R20-2 and R22-2 was similar. The deflection increased linearly to the load until reaching its peak value. Then the load decreased progressively with the increase of the deflection.
Load-strain relationship
The load-strain curves of the beams were shown in Fig. 8. The strain was measured by the strain gauges attached to the concrete and rebar surfaces. Negative strains represented compressive strains while positive strains represented tensile strains. As shown in Fig. 8a, the load-strain curves of the concrete at the bottom face elevated. The load-strain relationships were similar for all reinforcement ratios. The strain was linear at first followed by a nonlinear region. The nonlinear region started at the initiation of cracking. There is no abrupt change of strain at nonlinear region. The reason is that the steel fibres in the cement matrix resisted the tensile force after the initiation of cracking32. Unfortunately, most of the strain gauges attached to the bottom face of concrete came off due to the developing cracks. Thus, only load-strain relationship at strain from 0 to 700 με were shown in Fig. 8a.
Figure 8b shows that the strain of tensile rebars of all beams increased linearly at the beginning. Greater tensile strains were generated after the yielding of rebar occurred. It can be seen that the yielding point of tensile reinforcement increased as the reinforcement ratio increased. For the beams R12-1, R18-1 and R18-2, the tensile reinforcement yielded before the concrete crushed, indicating that the reinforcement ratio of these beams were under-reinforced. For the beams R20-2 and R22-2, as shown in Figs. 7 and 8, the load at the yield of tensile reinforcements closed to the load at the concrete crushed, indicating that the reinforcement ratios for R20-2 and R22-2 approached to balance-reinforced. The load-strain behaviour of tensile reinforcements is consistent to the failure modes of the concrete beams.
Ductility
The ductility of concrete beams can be quantified using the ductility index, which is expressed by the deflection ductility index, curvature ductility index or rotational ductility index32. Deflection of ductility index was adopted in this study as expressed in Eq. (2).
where µ is the ductility index of the member, Δu is the mid-span deflection at the ultimate load, and Δy is the mid-span deflection at the yielding load. The ductility index for all the beams are shown in Table 5.
It is well known that the natural brittleness of plain concrete disqualified it to be applied separately to the structure due to the requirement of ductility for safety. The addition of steel fibre increased the ductility of the NR beam to 2.55. The improvement of ductility by fibres has been discussed in previous studies47,48,49. The fibre reinforcement in a concrete mix can make complementary and additive contributions to tensile behaviour of the beam49. This is because the fibres induced the delay of macrocracks formation48. For the beams with rebar, the ductility decreased as the reinforcement ratio increased. The effect of the reinforcement ratio on the ductility of the beams is similar to previous studies35,50,51. This is because the tensile rebar yield before the concrete in the compression zone is crushed for low reinforcement ratio. As the reinforcement ratio increasing, the concrete will be crushed without prior yielding of tensile rebar, causing a brittle failure manner. Thus, the ductility of the beams decreased with the increase of reinforcement ratio35. However, the ductility indexes of beams R20-2 and R22-2 were less than that without rebar, indicating that the addition of steel fibre can improve the ductility of beams without reinforcement but weaken the ductility of beams with high reinforcement ratio. The reduced ductility index of beams with rebar by adding steel fibres was also reported in previous studies52,53. The reduction was caused by the smaller deflection capacity resulted from the crack bridging capability of fibres, leading to the decreases in differences between deflections at steel rebar yield and peak load54.
Estimation of bending moment capacity
In China, the bending moment capacity of UHPFRC members is predicted by the calculation model in CECS38-2004.
As shown in Fig. 9, the results of the compressive stress and tensile stress of concrete give:
The moment of the compressive stress resultant about the neutral axis is
Axial load equilibrium gives
where \(f_{y}\) is the tensile yield strength of steel rebar, \(A_{s}\) is the area of tensile longitudinal rebar, \(f_{y}^{^{\prime}}\) is the compressive yield strength of steel rebar, \(A_{s}^{^{\prime}}\) is the area of compressive longitudinal rebar, \(h\) is the depth of the beam cross-section, \(b\) is the width of the concrete section, \(x_{c}\) is the distance from the top to the neutral axis,\( f_{t}\) is the tensile strength of the concrete, \(f_{c}\) is the compressive strength of the concrete, \(\alpha_{1}\), \(\alpha_{2}\) and \(\beta\) are the coefficients defining the depth and average stress of the equivalent rectangular stress block.
The ultimate moment can be evaluated as
where \(a_{s}^{^{\prime}}\) is the distance from the top to the compressive steel rebar and \(h_{0}\) is the distance from the top to the tensile steel rebar.
Detailed properties of the beams are given in Table 6.
To calculate the ultimate moment of the concrete beams, the parameters \(\alpha_{2}\), \(\beta\) and \(x_{c}\) are needed to be determined. The equivalent of stress distribution at failure is from the assumption of stress distribution of cross-section at failure based on the constitutive relationship of UHPFRC at DBJ43T325-2017 as shown in Fig. 10.
The compressive stress and tensile stress resultant from the assumption of stress distribution at failure can be determined as follows.
\(F_{t - assumption} = \mathop \smallint \limits_{0}^{{h - x_{c} }} \sigma_{t} \left( y \right)bdy\) (9.
The moment of the compressive stress resultant about the neutral axis is
where \(\sigma_{c}\) is the compressive stress of concrete and \(\sigma_{t}\) the tensile stress of the concrete.
The parameters \(\alpha_{1}\) \(\alpha_{2}\), \(\beta\) and \(x_{c}\) can be determined by combing equations of (3), (4), (5), (6), (8), (9), and (10) as follows.
The value of parameters are summarized in Table 7. The details of calculating process are provided in "Appendix A".
Table 8 gives the experimental and predicted bending moment capacity. It can be seen that the experimental bending moment capacity of the UHPFRC beams with reinforcement ratio from 0 to 7.85% were underestimated while that with reinforcement ratio of 9.50% were overestimated. The reason why the bending moment capacity was overestimated is that the stress distribution of concrete was based on ductile failure of concrete beams. The concrete crushed and the steel yielded simultaneously. However, as discussed in previous sections, the concrete was crushed without prior yielding of the steel for concrete beam of R22-2, leading to smaller stress distribution of concrete when the concrete beam was failure. Thus, this calculation model is not suitable for the beams with high reinforcement ratio. The stress distribution at DBJ43T325-2017 should be modified to a lower value. A possible stress distribution of concrete is shown in Fig. 11.
Conclusion
The properties of UHPFRC specimens with different dimensions curing at different temperature and the flexural behaviour of UHPFRC beams with reinforcement ratio from 0 to 9.5% curing at room temperature were investigated in the present study. Moreover, test results were used to compare with the theoretical results based on the numerical models from the Chinese standards. The following conclusions can be made.
The materials and mix proportions can be used to manufacture UHPFRC specimens with compressive strength over 150 MPa at curing temperature of 90 °C. The compressive strength of cubic UHPFRC specimens significantly decreased with the decrease of curing temperature from 90 to 20 °C. The cubic compressive strength of specimen with dimension of 100 × 100 × 100 mm3 cured at 20 °C and the prismatic compressive strength of specimen with dimension of 100 × 100 × 300 mm3 cured at 20 °C were 102.90 MPa and 79.08 MPa, respectively. The tensile strength and flexural strength of UHPFRC specimens cured at 20 °C were 8.38 MPa and 17.7 MPa, respectively.
The bearing capacity of UHPFRC beams cured at 20 °C under flexure was enhanced as the increase of reinforcement ratio. The failure modes of UHPFRC beams changed from ductile to brittle as the reinforcement ratio increased from 1.26 to 9.5%. Moreover, the ductility of UHPFRC beams decreased with the increase of reinforcement ratio. The effect of reinforcement ratio on the flexural behaviour of UHPFRC beams cured at room temperature exhibited similar effect on those cured at high temperature. However, the standard strength level of UHPFRC specimens cannot be achieved at curing temperature of 20 °C. Although there is some reduction in strength, the UHPFRC beams cured at room temperature showed good performance and the flexural behaviour of these beams were in accordance with the UHPFRC beams cured at high temperature.
Compared to the test results of the bending moment capacity of UHPFRC beams at room temperature, the calculation model of CECS38-2004 underestimated the bending moment capacity of the under-reinforced UHPFRC beams (with reinforcement ratio from 0 to 7.85%) and overestimated the bending moment capacity of the UHPFRC beams with high reinforcement ratio of 9.50%. Thus, the calculation model of CECS38-2004 can be used to estimate the bending moment capacity of UHPFRC with low reinforcement ratios cured at room temperature for the safe purpose of practical engineering.
References
Recommendations, I., Association Française de Génie Civil. 2002, France.
AFGC-SETRA, U., Reinforced Concretes. Interim Recommendations, AFGC Publication, France, 2002.
Prem, P. R., Bharatkumar, B. & Iyer, N. R. Influence of curing regimes on compressive strength of ultra high performance concrete. Sadhana 38(6), 1421–1431 (2013).
Farnam, Y., Mohammadi, S. & Shekarchi, M. Experimental and numerical investigations of low velocity impact behavior of high-performance fiber-reinforced cement based composite. Int. J. Impact Eng 37(2), 220–229 (2010).
Shaikh, F.U.A., et al., Performance evaluation of Ultrahigh performance fibre reinforced concrete: a review. Constr. Build. Mater. 2020. 232: p. 117152.
Tam, C. M., Tam, V. W. & Ng, K. M. Assessing drying shrinkage and water permeability of reactive powder concrete produced in Hong Kong. Constr. Build. Mater. 26(1), 79–89 (2012).
Barnett, S. J. et al. Assessment of fibre orientation in ultra high performance fibre reinforced concrete and its effect on flexural strength. Mater. Struct. 43(7), 1009–1023 (2010).
Wille, K., Kim, D. J. & Naaman, A. E. Strain-hardening UHP-FRC with low fiber contents. Mater. Struct. 44(3), 583–598 (2011).
Yoo, D.-Y. et al. Biaxial flexural behavior of ultra-high-performance fiber-reinforced concrete with different fiber lengths and placement methods. Cement Concr. Compos. 63, 51–66 (2015).
Yoo, D.-Y., Kang, S.-T. & Yoon, Y.-S. Effect of fiber length and placement method on flexural behavior, tension-softening curve, and fiber distribution characteristics of UHPFRC. Constr. Build. Mater. 64, 67–81 (2014).
Kang, S.-T. et al. Tensile fracture properties of an Ultra High Performance Fiber Reinforced Concrete (UHPFRC) with steel fiber. Compos. Struct. 92(1), 61–71 (2010).
Ferrara, L., Ozyurt, N. & Di Prisco, M. High mechanical performance of fibre reinforced cementitious composites: the role of “casting-flow induced” fibre orientation. Mater. Struct. 44(1), 109–128 (2011).
Yoo, D.-Y. et al. Effect of fiber orientation on the rate-dependent flexural behavior of ultra-high-performance fiber-reinforced concrete. Compos. Struct. 157, 62–70 (2016).
Yoo, D.-Y., Kim, S.-W. & Park, J.-J. Comparative flexural behavior of ultra-high-performance concrete reinforced with hybrid straight steel fibers. Constr. Build. Mater. 132, 219–229 (2017).
Naaman, A. E. Engineered steel fibers with optimal properties for reinforcement of cement composites. J. Adv. Concr. Technol. 1(3), 241–252 (2003).
Wille, K. and A.E. Naaman, Pullout behavior of high-strength steel fibers embedded in ultra-high-performance concrete. ACI Mater. J., 2012. 109(4).
Zdeb, T. Ultra-high performance concrete–properties and technology. Bull. Polish Acad. Sci.: Tech. Sci. 61(1), 183–193 (2013).
Yazıcı, H. et al. Mechanical properties of reactive powder concrete containing mineral admixtures under different curing regimes. Constr. Build. Mater. 23(3), 1223–1231 (2009).
Wu, Z., Shi, C. & He, W. Comparative study on flexural properties of ultra-high performance concrete with supplementary cementitious materials under different curing regimes. Constr. Build. Mater. 136, 307–313 (2017).
Massidda, L. et al. High pressure steam curing of reactive-powder mortars. Special Publication 200, 447–464 (2001).
Wang, D., et al., A review on ultra high performance concrete: Part II. Hydration, microstructure and properties. Constr. Build. Mater., 2015. 96: p. 368–377.
Ahmad, S., Hakeem, I. & Azad, A. K. Effect of curing, fibre content and exposures on compressive strength and elasticity of UHPC. Adv. Cem. Res. 27(4), 233–239 (2015).
Habel, K. et al. Development of the mechanical properties of an ultra-high performance fiber reinforced concrete (UHPFRC). Cem. Concr. Res. 36(7), 1362–1370 (2006).
Wille, K. et al. Ultra-high performance concrete and fiber reinforced concrete: achieving strength and ductility without heat curing. Mater. Struct. 45(3), 309–324 (2012).
Yazıcı, H. The effect of curing conditions on compressive strength of ultra high strength concrete with high volume mineral admixtures. Build. Environ. 42(5), 2083–2089 (2007).
Yang, S. et al. Influence of aggregate and curing regime on the mechanical properties of ultra-high performance fibre reinforced concrete (UHPFRC). Constr. Build. Mater. 23(6), 2291–2298 (2009).
Hasgul, U. et al. Flexural behavior of ultra-high-performance fiber reinforced concrete beams with low and high reinforcement ratios. Struct. Concr. 19(6), 1577–1590 (2018).
Meda, A., Minelli, F. & Plizzari, G. A. Flexural behaviour of RC beams in fibre reinforced concrete. Compos. B Eng. 43(8), 2930–2937 (2012).
Yoo, D.-Y. & Yoon, Y.-S. Structural performance of ultra-high-performance concrete beams with different steel fibers. Eng. Struct. 102, 409–423 (2015).
Kodur, V. et al. Analysis of flexural and shear resistance of ultra high performance fiber reinforced concrete beams without stirrups. Eng. Struct. 174, 873–884 (2018).
Qiu, M., et al., Experimental investigation on flexural cracking behavior of ultrahigh performance concrete beams. Structural Concrete, 2020.
Yang, I. H., Joh, C. & Kim, B.-S. Structural behavior of ultra high performance concrete beams subjected to bending. Eng. Struct. 32(11), 3478–3487 (2010).
Singh, M. et al. Experimental and numerical study of the flexural behaviour of ultra-high performance fibre reinforced concrete beams. Constr. Build. Mater. 138, 12–25 (2017).
Mohammadhassani, M. et al. An experimental study on the failure modes of high strength concrete beams with particular references to variation of the tensile reinforcement ratio. Eng. Fail. Anal. 41, 73–80 (2014).
Pam, H., Kwan, A. & Islam, M. Flexural strength and ductility of reinforced normal-and high-strength concrete beams. Proc. Inst. Civ. Eng.-Struct. Build. 146(4), 381–389 (2001).
Toledo Filho, R., et al., Performance assessment of ultra high performance fiber reinforced cementitious composites in view of sustainability. Mater. Des. (1980–2015), 2012. 36: p. 880–888.
Charron, J.-P., Denarié, E. & Brühwiler, E. Transport properties of water and glycol in an ultra high performance fiber reinforced concrete (UHPFRC) under high tensile deformation. Cem. Concr. Res. 38(5), 689–698 (2008).
CECS38, C.S., Technical Specification for Fiber Reinforced Concrete Structures. CECS38, 2004.
China, M. Standard for test method of mechanical properties on ordinary concrete (China Architecture & Building Press, 2002).
DBJ43T325–2017, Technical Specification for Reactive Powder Concrete Structures. 2017, Ministry of Housing and Urban-Rural Development of Hunan Province: Hunan Province, China.
Dai, Y. et al. Characterization of tensile failure behaviour of magnesia refractory materials by a modified dog-bone shape direct tensile method and splitting tests. Ceram. Int. 46(5), 6517–6525 (2020).
Arora, A. et al. Fundamental insights into the compressive and flexural response of binder-and aggregate-optimized ultra-high performance concrete (UHPC). Cement Concr. Compos. 98, 1–13 (2019).
Chu, T., Ranson, W. & Sutton, M. A. Applications of digital-image-correlation techniques to experimental mechanics. Exp. Mech. 25(3), 232–244 (1985).
Pan, B., et al. Two-dimensional digital image correlation for in-plane displacement and strain measurement: a review. Meas. Sci. Technol. 2009. 20(6): p. 062001.
Kotsovos, M., Concrete. A brittle fracturing material. Matériaux et Construction, 1984. 17(2): p. 107.
Chen, S. et al. Flexural behaviour of rebar-reinforced ultra-high-performance concrete beams. Mag. Concr. Res. 70(19), 997–1015 (2018).
Kang, S.-T. et al. Hybrid effects of steel fiber and microfiber on the tensile behavior of ultra-high performance concrete. Compos. Struct. 145, 37–42 (2016).
Lawler, J. S., Zampini, D. & Shah, S. P. Microfiber and macrofiber hybrid fiber-reinforced concrete. J. Mater. Civ. Eng. 17(5), 595–604 (2005).
Banthia, N. et al. Fiber synergy in Hybrid Fiber Reinforced Concrete (HyFRC) in flexure and direct shear. Cement Concr. Compos. 48, 91–97 (2014).
Yang, I.-H., C. Joh, and K.-C. Kim, A comparative experimental study on the flexural behavior of high-strength fiber-reinforced concrete and high-strength concrete beams. Adv. Mater. Sci. Eng. 2018. 2018.
Jang, I.-Y. et al. On the ductility of high-strength concrete beams. Int. J. Concrete Struct. Mater. 2(2), 115–122 (2008).
Dancygier, A. N. & Berkover, E. Cracking localization and reduced ductility in fiber-reinforced concrete beams with low reinforcement ratios. Eng. Struct. 111, 411–424 (2016).
Yoo, D.-Y. et al. Feasibility of replacing minimum shear reinforcement with steel fibers for sustainable high-strength concrete beams. Eng. Struct. 147, 207–222 (2017).
Yoo, D.-Y. & Moon, D.-Y. Effect of steel fibers on the flexural behavior of RC beams with very low reinforcement ratios. Constr. Build. Mater. 188, 237–254 (2018).
Acknowledgements
This study was funded by the Water Resource Science and Technology Innovation Program of Guangdong Province (2017-28) and Guangzhou Science and Technology Project (201903010096).
Author information
Authors and Affiliations
Contributions
Jinlin Huang: Conceptualization, Data curation, Funding acquisition, Investigation, Methodology, Resources, Writing—original draft. Zhiying He: Investigation. Muhammad Basit Ehsan Khan: Formal analysis, Writing—review & editing. Xiaohong Zheng: Investigation. Zhibin Luo: Conceptualization, Formal analysis, Supervision, Writing—review & editing.
Corresponding author
Ethics declarations
Competing interests
The authors declare no competing interests.
Additional information
Publisher's note
Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Supplementary Information
Rights and permissions
Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/.
About this article
Cite this article
Huang, J., He, Z., Khan, M.B.E. et al. Flexural behaviour and evaluation of ultra-high-performance fibre reinforced concrete beams cured at room temperature. Sci Rep 11, 19069 (2021). https://doi.org/10.1038/s41598-021-98502-x
Received:
Accepted:
Published:
DOI: https://doi.org/10.1038/s41598-021-98502-x
Comments
By submitting a comment you agree to abide by our Terms and Community Guidelines. If you find something abusive or that does not comply with our terms or guidelines please flag it as inappropriate.