Abstract

The largest amount of energy in buildings is consumed to provide heating, cooling, and ventilation. Therefore, a practical solution such as using renewable energy sources can be considered to reduce energy costs and pollutants. In addition, architecture principles must be varied to utilize passive solar energy and also to reduce energy losses. In this research, a numerical study is presented to investigate the thermal behavior of TW-FR (Trombe wall placed in a fenestrated room) in the semiarid region of Tunisia. Computational fluid dynamic (CFD) simulation of fluid flow and heat transfer shows good agreement with published data in literature. The thermal comfort level was calculated according to ASHRAE (55-2013). The results show that (i) the normal Trombe wall cannot assure a satisfactory comfort level even in summer conditions and a higher vertical temperature gradient can take a value of 15°C, and the Trombe wall is shown to be more efficient in heating mode in the studied semi-arid region compared to cooling; (ii) the operative temperature for the coldest winter is between 17.85 and 19.85°C. The air temperature gradient in the comfort ranges between the head and feet is 2.3°C; and (iii) the Trombe wall is an excellent solution for Sousse city weather; it is suggested that the passive system (TW-FR) will be examined for a whole year to have a precise evaluation of its efficiency.

1. Introduction

The applications of renewable energies have fascinated the interest of many architects and engineers in recent days [1, 2]. Several researches have shown the potential of using solar energy for satisfying energy demands of buildings [35] and industries [6] to alleviate the pollutant emission crisis [7, 8].

A thermal mass storage that comprised of external glazing, dampers, and vent in order to provide required heating, cooling, and ventilation passively is so-called Trombe wall [9]. In winters, air enters into the cavity through a low vent. The temperature of the air is raised in the wall and transferred to the room through the cavity due to buoyancy effect. In summers, the Trombe wall is performing similar to solar chimney since the low glazing vent will be closed and the high vent is opened [10].

A set of instructions are provided for the Trombe wall design based on experimental and numerical investigations. In the first look, the Trombe wall is a promising approach to save energy and to maintain the indoor air quality. Experimental study of room equipped with Trombe wall is offered by [11] where they studied house natural ventilation in arid climate of Yazd, Iran, experimentally by studying different types of fins, namely, brass, copper, and aluminum. The results approved that using thermal fins enhanced the energy-saving efficiency of the Trombe wall by 3% and improved its natural convection heat transfer rate by 6% inside the channel.

Dong et al. presented a new configuration for the Trombe wall by installing an absorbent plate between the glass cover and the thermal storage wall and examined it in Harbin, China [12]. It was shown that this novel layout increased the thermal efficiency by 50% compared to traditional Trombe wall. Abbassi and Dehmani introduced internal thermal fins into a Trombe wall [13]. Wu et al. proposed a 2-dimensional model on air filtration and thermal performance of a PC-Trombe wall [14]. The authors reported that increasing the solar radiation had positive effect on the thermal efficiency and ambient temperature. On the other hand, the air inlet temperature and ambient wind velocity was decreased. Recently, Abdeen et al. carried out an investigation on the heat transfer and air flow of a Trombe wall under quasistate situation in a moderate typical winter week in Alexandria, Egypt [15].

Computational fluid dynamics (CFD) is a viable solution to evaluate the flow behavior and thermal conditions of different systems [16]. In buildings, CFD can be extensively used to analyze energy consumption and to model the system with respect to real values. Risberg et al. simulated the heat supply through ventilation ducts placed at the ceiling in Swedish houses with passive house standards [17].

Bajc et al. presented a 3D CFD modeling and analyzed temperature distribution in the Trombe wall and in the adjacent room in a moderate climate [18]. The authors optimized the Trombe applying various types of glassing on the outer side of the wall and reported that the Trombe wall could be a practical solution for use in Belgrade region.

Overall, it can be understood from the previously discussed publications that the Trombe wall has promising potential to be used in buildings in order to maintain desirable heating and cooling rates. Monitoring the preceding studies showed that there is no comprehensive study on evaluation of thermal comfort in a building where the Trombe wall was installed in semiarid climate.

The application of the Trombe wall in Tunisia is still uncommon due to the lack of information about energy performance and construction details that do not persuade the stake holders to implement this system. This research has this target to display the effect of the space air flow pattern of Trombe wall installed in a fenestrated room.

2. Numerical Analysis

2.1. Mathematical Model

The simulations are implemented in ANSYS CFX (15.0). The continuity (Equation (1)), momentum (Equation (2)), and energy (Equation (3)) equations applied to the model are as follows [19]: where indicates the water specific heat, shows the thermal conductivity, is the dynamic viscosity, and denotes density.

The turbulence kinetic energy () and its dissipation rate () can be calculated as follows [20]: where indicates the turbulence kinetic energy associated with gradients of the mean velocity and refers to the turbulence kinetic with regard to buoyancy. is the fluctuating dilatation, and are the Prandtl numbers, and , , and are constants.

Compared to other turbulence models, the model is less nonlinear and has simple convergence that makes it simple to provide a suitable initial guess.

The turbulent viscosity, , is obtained as where is a constant.

The values of , and are

2.2. Mesh Independence Study and Boundary Conditions

The model of passive house with Trombe wall is a simple room with the Trombe wall on its south side and has a dimension of of  m3. The Trombe wall is characterized by 0.3 m for the thickness, 0.3 m for air gap, and 2.4 m for height. The room is vacant and just heated by direct sunlight. The physical model of the system is exposed in Figure 1. The boundary condition details are summarized in Table 1.

The whole domain is modeled with a structured rectangular mesh in ANSYS, and the simulations were performed in CFX 15.0. The used turbulence model as discussed above was . It is assumed that a steady-state condition was executed. The independence of grid has been established. Six cases of meshes are tested, 62908, 112356, 132804, and 164388. From the velocity results showed in Figure 2, grid size and cell number independency happened after the mesh N°5 and it has been shown that continuing the computation after this mesh (N°5 (cells 132804)) just prolonged the computation and it is performed only for accuracy purposes.

2.3. Climatic Data of the Town of Sousse

The town of Sousse (35° 49 34 north, 10° 38 24 east) is placed at 143 km from Tunis, at the south, and an altitude of 25 m. In summer, the temperatures surpass 43°C in the shade, and the relative humidity is about 67%. In addition, the outside temperature frequently differs between 10°C and 20°C in the winter at day time and can drop less than 1°C at night with inadequate and uneven rain.

3. Results

Many cases were studied in order to examine the heating/cooling potential of a Trombe wall system. In particular, we considered two different modes: the first is the coldest winter day in the year (28/12/2019), and the second is a hot summer day in the same year (21/07/2019). Climatic conditions for Sousse (2019) are expressed in Table 2. The results are illustrated in a vertical plane at the center of the building. The results obtained are presented in figures with different values of the solar chimney depth in order to see the influence on the thermal efficiency of the system.

3.1. Validation of Computational Methods

To validate the mathematical model, the numerical results obtained by CFD are compared with the results of a traditional TW under the same conditions of the experimental studies [21]. The comparison of energy efficiencies of the Trombe walls for different solar radiation intensities was carried out between CFD results and experimental data and is shown in Figure 3. To evaluate the results, the relative error is used as an indicator. The RE between CFD and experimental results is calculated by

As shown in Figure 3, a perfect agreement between the results obtained from the model and the published results is observed and the highest value of RE is 7.29%.

3.2. Hot Summer Day

A typical hot day in summer (July) is selected, and simulation is performed under steady-state conditions. Figure 4 shows the temperature field in the room in the section located at ( m). Due to buoyancy, the cold air spreads at the floor level. This cold airflow is like a jet and persuades the surrounding air; the Trombe wall could reduce indoor air temperature on average of 6.1°C. In this case, the air temperature gradient between a horizontal plane at 0.2 m and the floor is 7°C which is very high, and this zone is warmer, and an overheating phenomenon in the room is also observed.

Figure 5 shows the raw velocity vector map after passing the glass cover; solar energy here has the first interaction with the system TW-FR. In the first hand, the solar energy is absorbed by the Trombe wall. As a result, by conduction, this energy is moved through the wall and the remaining is moved to the air in the channel by convection. The air moves from the bottom to the top of the channel caused by the chimney effect.

The highest air velocity is about 0.5 m/s. According to [22], we observed that the air velocity in the region occupied by the middle section of the domain is not exceeding 0.17 m/s and this is between the comfort ranges. This condition that the average state air velocity is below 0.2 m/s made the greatest situation for human comfort. According to [22], the velocities between 0.18 and 0.24 m/s are perceivable but still in the comfort zone in summer.

3.3. Cold Winter Day

In this section, the simulations are prepared for a typical winter day at the month of January. Figure 6 shows the temperature field in the room at ( m). Even though the radiation is very high at this day, it is sufficient to transfer the air in the channel. The average temperature for the central point of the room is 18.46°C. The higher temperature in the room is around 20°C, and the minimum is about 10°C. The internal temperature offered higher values than external temperature getting the difference of 6.45°C. It can be concluded from the simulations that the temperature inside reached higher temperature compared to outside in a large zone of the system which is a negative result and will drive the heat flux from inside of the room to ambient. This can see obviously the high temperatures near the wall.

Figure 7 shows that the maximum velocities are positioned near the roof and floor. This flow causes a temperature gradient between regions. A small vortex is produced at the corner close to the room outlet. Reverse flow patterns were strong near floor. A relatively small recirculation zone was created, and a flow was observed. We observed also that the air flow is characterized by a strong turbulence near the floor and roof. High air velocities existed; the highest velocity is about 0.34 m/s. The air velocity in the region where it is thought that will be occupied (the mid region of the domain) is not exceeding 0.21 m/s. According to [22], this result is between the comfort zones.

The numerical distribution of pressure (Figures 8 and 9) is completely hydrostatic and also slightly small compared to atmospheric pressure particularly in the lower part of the Trombe wall due to the loss at the inlet restriction. A slight difference in distribution of pressure is appreciated between the air gap and the room, mainly in areas of low inlet and outlet pressure of Trombe wall.

The turbulent kinetic energy is discussed in Figures 10 and 11. At the input side, viscosity degraded the turbulent kinetic energy. Since there is no speed gradient nor gradient, a balance is achieved between the convection heat transfer and dissipation rate in the transport equation.

4. Discussion

The most cited technique in the literature to explain the indoor thermal comfort in buildings is according to Fanger’s comfort model [23], which is also used in [22, 24]. Where the thermal comfort is frequently examined inside the occupied zone, the volume occupants normally use is the volume enclosed by two horizontal planes, one 0.1 m above floor level and the other 2.0 m above floor level. The local discomfort can be classified generally as per the following according to the current standards and ASHRAE Fundamentals Handbook.

4.1. Operative Temperature

It can be defined by the uniform temperature of a pretend black enclosure in which a person would exchange the same amount of heat by radiation and convection as in an actual nonuniform environment. It is calculated according to where is the ambient air temperature, the radiation temperature, and the air velocity.

4.2. Vertical Air Temperature Difference

Thermal discomfort may happen as a result of thermal stratification. Figure 12 demonstrates the estimated value of dissatisfied people with respect to air temperature gradient where the ankle level is colder than the head level.

The thermal comfort for room equipped with a Trombe wall was considered under the coldest winter day and the hot summer day. The main parameter shown in the figures was the operative temperature. The hot summer day gave a bad thermal comfort, and the temperature difference over the entire room is small. The operative temperatures were around 29-44°C in the horizontal plane (Figure 13). The numerical results also show higher vertical temperature gradients which can take a value of 15°C (Figure 14); the results show also that operative temperature in the room is not within the comfort range. This demonstrates that the normal Trombe wall cannot assure a satisfactory comfort level even in summer conditions. In this case, the air temperature gradient between head level and ankle level is 10°C which exceeds 3°C and the discomfort is sensed because the head level is warmer than the ankle level according to [22]. As a result, the typical Trombe wall cannot reduce the effect of heating in the summer season. Consequently, heating seasons in Tunisia should introduce some modification in the Trombe wall like the use of a water tank, which is part of the building’s wall or it must ventilate the room with air circulation open.

This case of the coldest winter day (Figure 15) shows the most irregular distribution, and the vertical temperature gradients in the occupied zone are fewer than 2.5°. The operative temperature for the coldest winter is between 17.85 and 19.85°C. The air temperature gradient between the head and feet is 2.3°C. Based on [22], this is between the comfort ranges and 5% of occupants are dissatisfied by the vertical air stratification.

5. Conclusion(s)

The following remarks can be concluded from this study: (i)The CFD simulation is able to provide accurate air temperature and velocity distributions inside the building room(ii)It was observed from the simulations that installing the Trombe wall can highly influence the temperature distribution inside the modeled house for Sousse city weather information(iii)It was shown that installing the Trombe wall had significant influence on the temperature of the room that it was kept around 20°C in winter conditions(iv)However, in summer conditions, a normal Trombe wall can be considered an additional source of heating for the building(v)The typical Trombe wall cannot reduce the effect of heating in the summer season. Consequently, during hot seasons in Tunisia, some modifications in the Trombe wall should be introduced

Nomenclature

:Time (s)
:Turbulent kinetic energy (m2/s2)
:Turbulent mixing length (m)
:Cartesian coordinate index
:Constant pressure specific heat (J/kgK)
:Temperature (K)
:Thermal conductivity (w/mK)
:Gravity acceleration (m/s2)
:Body force (N/m3)
CFD:Computational fluid dynamics
:Constants
:Constants
:Buoyancy kinetic energy (kg/m s3)
:Velocity gradients turbulent kinetic energy (kg/ms3)
:Effective viscosity (m2/s)
:Contribution of the fluctuating dilatation in compressible turbulence to the overall dissipation rate (kg/m s2)
:Mass source (kg/m3)
:Specific heat (J/kgK)
:Characteristic length (m)
Pr:Prandtl number
Gr:Grashof number
:Radiation temperature (K)
:Ambient temperature (K).
Greek Symbols
:Turbulent Prandtl
:Kinematic viscosity (m2/s)
:Thermal diffusivity (m2/s)
:Thermal expansion coefficient (K-1)
:Turbulent dissipation rate (m2/s3)
:Turbulent kinetic energy (m2/s2)
:Kronecker delta.