Article

Protection of Sensitive Loads in Distribution Systems Using a BSFCL-DVR System

by
Mehdi Firouzi
1,*,
Saleh Mobayen
2,3,*,
Hossein Shahbabaei Kartijkolaie
4,
Mojtaba Nasiri
5 and
Chih-Chiang Chen
6
1
Department of Electrical Engineering, Faculty of Engineering, Abhar Branch, Islamic Azad University, Abhar 1584743311, Iran
2
Advanced Control Systems Laboratory, Department of Electrical Engineering, University of Zanjan, University Blvd., Zanjan 4537138791, Iran
3
Future Technology Research Center, National Yunlin University of Science and Technology, 123 University Road, Section 3, Douliou, Yunlin 64002, Taiwan
4
Golestan Provinace Distribution Electrical Company, Gorgan 517212, Iran
5
Solar Energy Applications Group, Trinity College Dublin, University of Dublin, D02 PN40 Dublin, Ireland
6
Department of Systems and Naval Mechatronic Engineering, National Cheng Kung University, Tainan 70101, Taiwan
*
Authors to whom correspondence should be addressed.
Sensors 2021, 21(5), 1615; https://doi.org/10.3390/s21051615
Submission received: 21 January 2021 / Revised: 16 February 2021 / Accepted: 22 February 2021 / Published: 25 February 2021
(This article belongs to the Section Electronic Sensors)

Abstract

:
In this paper, an incorporated bridge-type superconducting fault current limiter (BSFCL) and Dynamic Voltage Restorer (DVR) is presented to improve the voltage quality and limiting fault current problems in distribution systems. In order to achieve these capabilities, the BSFCL and DVR are integrated through a common DC link as a BSFCL-DVR system. The FCL and DVR ports of the BSFCL-DVR system are located in the beginning and end of the sensitive loads’ feeder integrated to the point of common coupling (PCC) in the distribution system. At first, the principle operation of the BSFCL-DVR is discussed. Then, a control system for the BSFCL-DVR system is designed to enhance the voltage quality and limit the fault current. Eventually, the efficiency of the BSFCL-DVR system is verified through the PSCAD/EMTDC simulation.

1. Introduction

The expansion and complexity of modern power systems, as well as emergent technologies and power quality problems, make the design and engineering of distribution systems challenging [1]. Among all power quality problems, momentary outages, and voltage sag are the most important ones. For sensitive loads, even a shallow voltage dip can cause malfunction and operation failure [2,3]. Furthermore, the most voltage sags mainly occur due to the distribution system downstream short circuit faults [4]. The distribution system topology is one of the main factors for voltage sag depth and duration. A large fault current in a feeder of parallel feeders results in voltage sag at the point of common coupling (PCC), which affects the loads in other parallel feeders connected to the PCC. The main adverse effects of voltage sags are [5,6,7,8,9]:
  • Malfunction of protection equipment
  • Tripping of process control and desktop computers
  • Costly production wastage due to interruption of process materials
  • Malfunction of wind turbine grid-side converters
Therefore, researchers are studying techniques to suppress the fault current and reduce the voltage sag under fault condition [8,9,10]. It is generally less costly to tackle the problem at its lowest level, i.e., close to the load. In [11], a dual-function dynamic voltage restorer (DVR) is proposed to mitigate voltage sag and fault current level in distribution system. To achieve this capability, the flux-charge feedback-based control system is implemented to the DVR, which acts as large inductance to limit downstream fault currents. In [12], a dual-functional bridge-type fault current limiter (BTFCL) is presented and designed, which can operate in both current limiting modes to reduce faulty currents and DVR mode to compensate the voltage sag in distribution system. In [13], a new FCL-DVR scheme is proposed, which can operate with different protection strategies under grid disturbances. It includes a crowbar bidirectional-thyristor switch, which is located in the output of DVR to limit the fault currents. All design considerations of the FCL-DVR parameters including power rating of DVR converter, output filter reactors and the DC link capacitor are presented. In [14], a novel FCL-DVR concept is proposed, which both capabilities of limiting fault current and compensating the PCC voltage. The main advantage of proposed FCL-DVR concept is its reduced number of components compared to the other FCL-DVR schemes. In [15], an improved FCL-DVR scheme with energy-optimized control strategy is proposed, which has both capabilities of other FCL-DVR schemes with the capacity optimization of its key components.
In [16], a voltage-booster scheme includes the DVR and high-temperature superconducting FCL (HTS-FCL) are designed and implemented to the doubly-fed induction generator (DFIG) for enhancing the fault-ride through (FRT) performance. In [17], the unified inter-phase power controller (UIPC) is used to control power flow in hybrid AC/DC micro-grid. In [18], a multi-step braking resistor is proposed to enhance the FRT performance of fixed-speed wind turbines. In [19], a multi-resistor BFCL (MRBFCL) is proposed to mitigate the PCC voltage under different voltage sag levels. In this configuration multi resistors has been used instead of single resistor in the conventional BFCL in [20]. It is implemented to the DFIG [19] and permanent-magnet synchronous generator (PMSG)-based [19] wind turbines for enhancing the FRT, respectively. Authors in [21] presents a dynamic multi-cell BFCL to compensate the PCC voltage of wind farms. It is connected between the wind farm and grid without using coupling transformer and can compensate the PCC voltage under whole voltage sag level. In [22], a superconducting-based FCL and a MW class DVR integrated with superconducting-magnetic energy-storage (SMES) system are presented for voltage sag compensation in distribution system. Considering this background, this paper proposes a new solution based on superconductive and power electronic devices for limiting fault current and compensating the PCC voltage in distribution systems.
Several solutions based on superconductive and power electronic devices have been reported in [23,24,25,26,27,28,29,30]. In [29], a combination of series phase shifter (SPS) with SMES has been suggested to enhance the transient stability in the power system. In [24], a combination of SMES with Static synchronous compensator has been used for improving wind turbine generation system stability. In [25], the combined SMES and solid-state phase shifter have been proposed to enhancement the control of the system. In [26], a novel combined device has been presented, which is connected in series with two independent power systems. The voltage regulation is the main function of this device. In [27,28], a combined superconducting fault current limiter (SFCL) and SMES has been proposed to suppress the fault current and improve the transient behavior in a microgrid.
In this paper, a bridge-type SFCL (BSFCL) and a dynamic voltage restorer (DVR) are combined to create new dual-functional equipment as a BSFCL-DVR system for limiting the fault current and improvement of the voltage quality. The schematic diagram of the BSFCL-DVR is shown in Figure 1. It is connected at the beginning and end of the feeder supplying a sensitive load. The following desired features can be mentioned for the proposed structure:
  • The superconducting coil can be used as an energy storage device in the DVR and limiting element in BSFCL. The proposed BSFCL-DVR system needs only one superconducting coil.
  • The BSFCL only limits the transient fault current at the beginning time of fault and cannot limit the amplitude of the fault current. However, by using the BSFCL-DVR system, the fault current amplitude is limited as well as transient fault current.
  • The DVR of the proposed structure can compensate steady-state load voltage under both normal and fault conditions.
  • It can compensate sensitive load voltages during fault and prevent from a system outage.
  • The voltage quality at the PCC is compensated; therefore the loads on parallel feeders would not affect during the fault period.
  • The proposed BSFCL-DVR system increases the reliability of sensitive loads.
Figure 1. BSFCL-DVR system.
Figure 1. BSFCL-DVR system.
Sensors 21 01615 g001
However, the disadvantages of the BSFCL-DVR system are high compensation capacity voltage source inverter (VSI) for the DVR port and additional communication with the protection system as fault detection function. In this paper, the power circuit and principle operation of the BSFCL are presented in Section 2. The brief description of DVR is presented in Section 3. In Section 4, the proposed structure is given. Section 5 proves the new BSFCL-DVR performance by comparing it in three cases on the PSCAD/EMTDC. Eventually, the conclusions of this study are presented in Section 5.

2. Bridge-Type SFCL

Different types of FCL including SFCLs, solid state FCLs (SSFCLs) and resonant-type FCLs (RFCLs) have been proposed and documented in literature [29,30]. The application of SFCLs was found as promising solution to limit fault current and also can increase the reliability of system [31], enhance the power quality in distribution system [32], mitigate the transformer inrush currents [33], mitigate the transient over voltages [34], and improve the power system transient stability [35]. They are classified in to three resistive-type, inductive-type and bridge-type SFCL (BSFCL). This bridge-type SFCL consists of high-temperature superconducting coil (HTSC) and a diode bridge rectifier. Superconductors are used to limit fault current in both AC and DC grids with significant advantages such as compact size and high efficiency [36,37]. The BSFCL has specific characteristics including:
  • It can suppress the transient fault current at the beginning time of fault without any delay;
  • It requires any fault detection and controller system;
  • It prevents from happening instantaneously deep voltage drop at the beginning time of the fault.
The major disadvantage of BSFCL is that it cannot stop gradually increase of the fault current.

2.1. Power Circuit of Bridge-Type SFCL

In Figure 1, the BSFCL power circuit is represented. It includes the following parts:
  • Three coupling transformers (Ta, Tb, and Tc).
  • Three-phase bridge rectifier (D1–D6) to converts the AC line current to DC current (id)
  • A superconducting coil (SC) is connected to the DC side of the bridge rectifier circuit as limiting impedance [38,39,40,41].

2.2. BSFCL Characteristic

Figure 2b shows the test circuit, which is employed for analytical studies. The source and load impedances are presented by   Z s = r s + j ω L s and Z L = r L + j ω L L . The transformer turn ratio is assumed to be 1. Figure 2c demonstrates the line and SC currents in the presence of the BSFCL. As demonstrated in this figure, the current of the SC is approximately constant in the normal condition and, we have:
V d = L d d i d d t = 0
Therefore, the BSFCL does not affect the line side under this condition. Once, a short circuit fault happens at t = t0, the SC current (id) and subsequently the line fault current (iL) starts to increase with a constant rate. The performance of the BSFCL is divided into two periods. In the first period t0 < t < t1, both SC and line currents are equal. The KVL law to obtain the line current (iL) is given by:
2   V   s i n ω t = r i L +   L d i L d t
where   r = r s and L = L s + L d . Considering (2), the iL, is determined, as follows:
i L = e r L t t 0 i 0 2 V Z sin ω t φ + 2 V Z sin ω t φ
where, i 0 = i L t = t 0 , Z = r 2 + L ω 2 and t a n φ = L ω / r . In the second period t1 < t < t2, the id is higher than the iL. Therefore, the id flows through the diodes. The currents id and iL are presented as follows:
i d = e r L t t 1 i 1
and
i L = e r L t t 1 i 1 2 V Z sin ω t φ + 2 V Z sin ω t φ
where i 1 = i L t = t 1 , Z = r 2 + L ω 2 , t a n φ = L ω / r ,   r = r s , and L = L s .

3. Dynamic Voltage Restorer

Figure 3 represents the DVR power circuit. It can protect the sensitive loads from destructive effects of voltage drop. It essentially consists of an injection transformer, a low pass filter to eliminate the high order harmonics, which represented by Lf and Cf, a voltage source inverter (VSI), and an energy storage system (ESS). In this paper, the pulse-wide-modulation (PWM) technique is used to control the VSI. To restitute the load voltage at the pre-fault time, the DVR will inject a voltage to compensate the voltage drop. In order to increase the voltage, the active power capacity of the ESS is a limiting factor. This is important, especially for mitigating long duration voltage sag [42,43]. To compensate the voltage sag by the DVR, several control techniques have been proposed in the literature. They are classified into pre-sag [42], in-phase [43], and minimal energy [44] methods.
The sensitive loads characteristic is the main factor to determine the control method. In the in-phase control method, the VDVR is injected in-phase with source-side voltage (Vs), regardless of the pre-fault voltage and the load current. The amplitude of the injection voltage is the main advantage of this method [42,43]. In the minimal energy method, the injected voltage by the DVR is perpendicular to the load current. Therefore, it does not require active power to raise the voltage [44,45]. The nonlinear loads are vulnerable to phase jumps in the voltage drop condition [44]. The pre-sag compensation strategy is applied to overcome this problem by increasing the instantaneous load voltage to the pre-sag voltage phase and magnitude [42].

4. Proposed Structure

Figure 4 shows the BSFCL-DVR power circuit. It is mainly composed of three single-phase VSIs (i.e., IGBT G1G4, G5G8, and G9G12), inverter output filter (LfCf), bridge rectifier circuit (D1D6), a boost regulator (MOSFET T and diode Dm), SC coil (Ld). DC link (C), which is located between the DVR and boost converter. The DVR is located into the load side through three boost transformers (TA, TB, TC) at the end of the feeder, which are the DVR function port. Transformers (Ta, Tb, Tc) are integrated into the SC coil via a three-phase bridge rectifier circuit as an FCL port. Under the operation mode of the grid, the T is closed and the DVR port is used to compensate the load voltage. The current following through the SC is approximately constant, so the FCL port does not effect on the line side.
Figure 5 shows the gating signal of the T, operation of the boost chopper for charging the capacitor when T is on and off states under fault condition, respectively. In the fault condition, the circuit operation is divided into two modes. The first mode is shown in Figure 5b. In this mode, T is on and the input voltage across the SC, i.e., Vd is equal to the voltage across the SC and id linearly increases, which leads to raising of energy in the SC. In the second mode, the T is turned off and the SC current flows through the diode (Dm) as demonstrated in Figure 5c. Also, some of the SC energy is transferred to the capacitor and id linearly decreases as shown in Figure 5a. By appropriate switching of T, the DC link voltage remains constant. Simultaneously, the DVR converter injects the AC voltage to the line at the end of the feeder at the load side.

Control Strategy

The main functions of the new structure are limiting fault current and compensate the load voltage during a fault condition. The DVR port restored the load voltage to its desired level. In this paper, the phase-locked loop (PLL) synchronization method has been used. Figure 6a demonstrates the block diagram of the PLL, which includes the voltage-controller oscillator (VCO), a phase detector (PD), and a loop filter (LF). Under the fault condition, the PCC voltage (VPCC) is controlled based on the pre-sag compensation strategy. Figure 6b demonstrates the control scheme of the DVR port. The main drawback of this method is the capacity limitation of the ESS to support active power for compensation the voltage sag. But, the BSFCL-DVR system solves this drawback. In the proposed method, the boost converter provides constant DC voltage for the capacitor with absorbing the SC energy stored. Figure 6c,d show the control scheme of the boost chopper regulator and the phasor diagram of the DVR port.

5. Simulation Results

The simulated system is shown in Figure 7. Simulation studies were performed in PSCAD/EMTDC software to investigate the efficiency of the BSFCL-DVR system. The parameters of the studied system are given in Table 1.
Simulations have been performed for three following cases:
Case A:
No FCL is in operation,
Case B:
Conventional BSFCL is in operation and,
Case C:
DVR-BSFCL is employed.

5.1. Case A

In case A, a three-line-to-ground (3LG) fault happens at t = 0.5 s on feeder 2 (F2). Figure 8a,b demonstrate the line current of F2 and the PCC voltage without using any FCL. As illustrated in Figure 8a,b, the fault current is increased to the peak value of 8 kA and the PCC voltage falls to zero, approximately.

5.2. Case B

Figure 9a,b demonstrate the line current of F2 and the PCC voltage with using conventional BSFCL in the mentioned fault condition. As demonstrated in Figure 9a, that the transient fault current is limited, however, the fault current increases gradually during the fault period. Also, it causes the PCC voltage sag gradually to increase. To compare the harmonic of VPCC, Table 2 is presented. As shown in Table 2, in case B (conventional BSFCL), The THD of VPCC is 25%. Additionally, it also includes both even and odd harmonics. Furthermore, the amplitude of the fundamental component is low. It is quite obvious that the conventional BSFCL can limit the fault current; however, it cannot satisfy the requirements of the IEEE 519 standard for the PCC voltage. However, the sensitive loads on F2 experience power outage during the fault.

5.3. Case C

Figure 10a,b illustrate the load voltage and the injected voltage by DVR port in F2 during the fault, respectively. As shown in Figure 10a, by using the proposed DVR-BSFCL structure, the load voltage is compensated to pre-fault voltage in F2. Figure 10c,d show PCC voltage and capacitor voltage, respectively. Although the PCC voltage is distorted during the fault, it is protected from voltage sag.
Figure 11 shows the load and fault currents of F2. As shown in Figure 11a, the load current would not be affected by fault occurring and it is protected from momentary outages during the fault. However, the fault current in the F2 effectively is limited by the FCL port and is not increased gradually during the fault. As shown in Table 2, the relative amplitude of harmonic components of PCC voltage in case C is much less than case B. Figure 12a shows the current of common loads connected to PCC during the fault, respectively. It is obvious from Figure 12a that the load current of F1 is protected from voltage sag and momentary outage during the fault. Figure 12b,c show the SC coil current and enlargement SC current during fault, respectively.

6. Conclusions

This paper presents a new combined BSFCL-DVR system to protect the PCC voltage and limits fault current in distribution including multi feeder connected to the PCC bus. It requires only one superconducting energy storage, which reduces the cost of using this device in distribution system. It has two FCL and VDR ports, which is interlined between the beginning and end of feeders. In the normal condition, the FCL port does not affect system performance and DVR port compensates the load voltage. In the fault condition, the fault current is effectively limited by FCL port and the voltage of sensitive loads have been compensated in pre-fault voltage by DVR port, simultaneously. Additionally, the PCC voltage remains at an acceptable level and the other connected loads to the PCC continue their safe operation.

Author Contributions

Conceptualization, investigation, and writing—original draft preparation: M.F., H.S.K. and M.N.; writing—review and editing, and supervision: S.M. and C.-C.C. All authors have read and agreed to the published version of the manuscript.

Funding

The authors received no financial support for the research, authorship, and/or publication of this article.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data that support the findings of this study are available within the article.

Acknowledgements

This work was supported in part by the Ministry of Science and Technology (MOST), Taiwan, under Grant MOST 109-2221-E-006-089-.

Conflicts of Interest

The authors declare that they have no conflict of interest.

References

  1. Bassan, F.R.; Rosolem, J.B.; Floridia, C.; Aires, B.N.; Peres, R.; Aprea, J.F.; Nascimento, C.A.M.; Fruett, F. Power-over-Fiber LPIT for Voltage and Current Measurements in the Medium Voltage Distribution Networks. Sensors 2021, 21, 547. [Google Scholar] [CrossRef] [PubMed]
  2. Pointl, M.; Fuchs-Hanusch, D. Assessing the Potential of LPWAN Communication Technologies for Near Real-Time Leak Detection in Water Distribution Systems. Sensors 2021, 21, 293. [Google Scholar] [CrossRef]
  3. Tosato, F.; Quaia, S. Reducing voltage sags through fault current limitation. IEEE Trans. Power Deliv. 2001, 16, 12–17. [Google Scholar] [CrossRef]
  4. Martinez, J.; Martin-Arnedo, J. Voltage Sag Studies in Distribution Networks—Part I: System Modeling. IEEE Trans. Power Deliv. 2006, 21, 1670–1678. [Google Scholar] [CrossRef]
  5. Martinez, J.; Martin-Arnedo, J. Voltage Sag Studies in Distribution Networks—Part II: Voltage Sag Assessment. IEEE Trans. Power Deliv. 2006, 21, 1679–1688. [Google Scholar] [CrossRef]
  6. Morandi, A. Fault Current Limiter: An Enabler for Increasing Safety and Power Quality of Distribution Networks. IEEE Trans. Appl. Supercond. 2013, 23, 57–64. [Google Scholar] [CrossRef]
  7. Firouzi, M. A modified capacitive bridge-type fault current limiter (CBFCL) for LVRT performance enhancement of wind power plants. Int. Trans. Electr. Energy Syst. 2018, 28, e2505. [Google Scholar] [CrossRef]
  8. Naghibi, S.E.; Mirzaie, M.; Barforoshi, T. Interline bridge-type fault current limiter: A novel approach for limiting fault current in distribution network. Int. Trans. Electr. Energy Syst. 2020, 30. [Google Scholar] [CrossRef]
  9. Heidary, A.; Radmanesh, H.; Rouzbehi, K.; Cheshmehbeigi, H.M. A Multifunction High-Temperature Superconductive Power Flow Controller and Fault Current Limiter. IEEE Trans. Appl. Supercond. 2020, 30, 1–8. [Google Scholar] [CrossRef]
  10. Ghanbari, T.; Farjah, E.; Naseri, F. Power quality improvement of radial feeders using an efficient method. Electr. Power Syst. Res. 2018, 163, 140–153. [Google Scholar] [CrossRef]
  11. Li, Y.W.; Vilathgamuwa, D.M.; Loh, P.C.; Blaabjerg, F. A Dual-Functional Medium Voltage Level DVR to Limit Downstream Fault Currents. IEEE Trans. Power Electron. 2007, 22, 1330–1340. [Google Scholar] [CrossRef]
  12. Jiang, F.; Cheng, S.; Tu, C.; Guo, Q.; Zhu, R.; Li, X.; Liserre, M. Design Consideration of a Dual-Functional Bridge-Type Fault Current Limiter. IEEE J. Emerg. Sel. Top. Power Electron. 2019, 8, 3825–3834. [Google Scholar] [CrossRef]
  13. Shuai, Z.; Yao, P.; Shen, Z.J.; Tu, C.; Jiang, F.; Cheng, Y. Design Considerations of a Fault Current Limiting Dynamic Voltage Restorer (FCL-DVR. IEEE Trans. Smart Grid 2015, 6, 14–25. [Google Scholar] [CrossRef]
  14. Ghavidel, P.; Farhadi, M.; Dabbaghjamanesh, M.; Jolfaei, A.; Sabahi, M. Fault Current Limiter Dynamic Voltage Restorer (FCL-DVR) with Reduced Number of Components. IEEE J. Emerg. Sel. Top. Ind. Electron. 2021. [Google Scholar] [CrossRef]
  15. Guo, Q.; Tu, C.; Jiang, F.; Zhu, R.; Gao, J. Improved Dual-Functional DVR with Integrated Auxiliary Capacitor for Capacity Optimization. IEEE Trans. Ind. Electron. 2020. [Google Scholar] [CrossRef]
  16. Alaraifi, S.; Moawwad, A.; El Moursi, M.S.; Khadkikar, V. Voltage Booster Schemes for Fault Ride-Through Enhancement of Variable Speed Wind Turbines. IEEE Trans. Sustain. Energy 2013, 4, 1071–1081. [Google Scholar] [CrossRef]
  17. Zolfaghari, M.; Abedi, M.; Gharehpetian, G.B. Power Flow Control of Interconnected AC–DC Microgrids in Grid-Connected Hybrid Microgrids Using Modified UIPC. IEEE Trans. Smart Grid 2019, 10, 6298–6307. [Google Scholar] [CrossRef]
  18. Goweily, K.; el Moursi, M.S.; Rahman, M.A.; Badr, M.A. Voltage booster scheme for enhancing the fault ride-through of wind turbines. IET Power Electron. 2015, 8, 1853–1863. [Google Scholar] [CrossRef]
  19. Firouzi, M.; Nasiri, M.; Benbouzid, M.; Gharehpetian, G.B. Application of multi-step bridge-type fault current limiter for fault ride-through capability enhancement of permanent magnet synchronous generator-based wind turbines. Int. Trans. Electr. Energy 2020, 30, e12611. [Google Scholar] [CrossRef]
  20. Firouzi, M.; Nasiri, M.; Mobayen, S.; Gharehpetian, G.B. Sliding Mode Controller-Based BFCL for Fault Ride-Through Performance Enhancement of DFIG-Based Wind Turbines. Complexity 2020, 2020, 1–12. [Google Scholar] [CrossRef]
  21. Shafiee, M.R.; Kartijkolaie, H.S.; Firouzi, M.; Mobayen, S.; Fekih, A. A Dynamic Multi-Cell FCL to Improve the Fault Ride through Capability of DFIG-Based Wind Farms. Energies 2020, 13, 6071. [Google Scholar] [CrossRef]
  22. Zheng, Z.; Xiao, X.; Huang, C.; Li, C. Enhancing Transient Voltage Quality in a Distribution Power System with SMES-Based DVR and SFCL. IEEE Trans. Appl. Supercond. 2019, 29, 1–5. [Google Scholar] [CrossRef]
  23. Kamolyabutra, D.; Mitani, Y.; Tsuji, K. Power system stabilizing control and current limiting by a SMES with a series phase compensator. IEEE Trans. Appl. Supercond. 2001, 11, 1753–1756. [Google Scholar] [CrossRef]
  24. Suvire, G.O.; Mercado, P.E. Combined control of a distribution static synchronous compensator/flywheel energy storage system for wind energy applications. IET Gener. Transm. Distrib. 2012, 6, 483–492. [Google Scholar] [CrossRef]
  25. Kamolyabutra, D.; Mitani, Y.; Ise, T.; Tsuji, K. Experimental study on power system stabilizing control scheme for the SMES with solid-state phase shifter (SuperSMES). IEEE Trans. Appl. Supercond. 1999, 9, 326–329. [Google Scholar] [CrossRef] [Green Version]
  26. Zhu, G.; Wang, Z.; Jiang, X. Design and Research on a Multi-Functional Combined Device Incorporating a SMES. IEEE Trans. Appl. Supercond. 2007, 17, 2018–2021. [Google Scholar]
  27. Zhu, G.; Wang, Z.; Liu, X.; Zhang, G.; Jiang, X. Transient Behavior Research on the Combined Equipment of SMES-SFCL. IEEE Trans. Appl. Supercond. 2004, 14, 778–781. [Google Scholar] [CrossRef]
  28. Chen, L.; He, H.; Zhu, L.; Guo, F.; Shu, Z. Coordinated Control of SFCL and SMES for Transient Performance Improvement of Microgrid With Multiple DG Units. Can. J. Electr. Comput. Eng. 2016, 39, 158–167. [Google Scholar] [CrossRef]
  29. Ghanbari, T.; Farjah, E.; Zandnia, A. Development of a high-performance bridge-type fault current limiter. IET Gener. Transm. Distrib. 2014, 8, 486–494. [Google Scholar] [CrossRef]
  30. Moghimian, M.M.; Radmehr, M.; Firouzi, M. Series Resonance Fault Current Limiter (SRFCL) with MOV for LVRT Enhancement in DFIG-Based Wind Farms. Electr. Power Compon. Syst. 2020, 47, 1814–1825. [Google Scholar] [CrossRef]
  31. Kim, S.-Y.; Kim, J.-O.; Bae, I.-S.; Cha, J.-M. Distribution Reliability Evaluation Affected by Superconducting Fault Current Limiter. In Proceedings of the IEEE/PES Transmission and Distribution Conference and Exposition, Sao Paulo, Brazil, 8–10 November 2010. [Google Scholar]
  32. Radmanesh, H.; Fathi, S.H.; Gharehpetian, G.B.; Heidary, A. Bridge-Type Solid-State Fault Current Limiter Based on AC/DC Reactor. IEEE Trans. Power Deliv. 2015, 31, 200–209. [Google Scholar] [CrossRef]
  33. Seo, H.; Kim, C.; Rhee, S.; Kim, J.; Hyon, O.B. Superconducting Fault Current Limiter Application for Reduction of the Transformer Inrush Current: A Decision Scheme of the Optimal Insertion Resistance. Trans. Appl. Supercond. 2010, 20, 2255–2264. [Google Scholar] [CrossRef]
  34. BatistadeSousa, W.T.; Kottonau, D.; Geisbuesch, J.; Karrari, S.; Noe, M. Deployment of a Resistive Superconducting Fault Current Limiter for Improvement of Voltage Quality and Transient Recovery Voltage. IEEE Trans. Appl. Supercond. 2020, 31. [Google Scholar] [CrossRef]
  35. Shirai, Y.; Furushiba, K.; Shouno, Y.; Shiotsu, M.; Nitta, T.; Shirai, Y.; Taguchi, M. Improvement of Power System Stability by Use of Superconducting Fault Current Limiter with ZnO Device and Resistor in Parallel. Trans. Appl. Supercond. 2008, 18, 680–683. [Google Scholar] [CrossRef]
  36. Song, W.; Pei, X.; Xi, J.; Zeng, X. A Novel Helical Superconducting Fault Current Limiter for Electric Propulsion Aircraft. IEEE Trans. Transp. Electrif. 2021. [Google Scholar] [CrossRef]
  37. Song, W.; Pei, X.; Zeng, X.; Yazdani-Asrami, M.; Fang, X.; Fang, J.; Jiang, Z. AC Losses in Noninductive SFCL Solenoidal Coils Wound by Parallel Conductors. Trans. Appl. Supercond. 2020, 30. [Google Scholar] [CrossRef]
  38. Tseng, H.; Chen, J. Quasi-bridge-type fault current limiter for mitigating fault transient phenomena. IET Gener. Transm. Distrib. 2014, 8, 1377–1391. [Google Scholar] [CrossRef]
  39. Kim, H.-R.; Yang, S.-E.; Yu, S.-D.; Kim, H.; Park, B.-J.; Han, Y.-H.; Park, K.; Yu, J. Development and Grid Operation of Superconducting Fault Current Limiters in KEPCO. IEEE Trans. Appl. Supercond. 2014, 24. [Google Scholar] [CrossRef]
  40. Kim, J.S.; Kim, J.C.; Lim, S.H. Study on Protection Coordination of a Flux-Lock-Type Superconducting Fault Current Limiter Using Switches. IEEE Trans. Appl. Supercond. 2016, 26. [Google Scholar] [CrossRef]
  41. Sato, T.; Yamaguchi, M.; Terashima, T.; Fuku, S.; Ogawa, J.; Shimizu, H.; Sato, T. Study on the Effect of Fault Current Limiter in Power System with Dispersed Generators. IEEE Trans. Appl. Supercond. 2007, 17, 2331–2334. [Google Scholar] [CrossRef]
  42. Choi, S.S.; Li, B.H.; Vilathgamuwa, D.M. Dynamic voltage restoration with minimum energy injection. IEEE Trans. Power Syst. 2000, 15, 51–57. [Google Scholar] [CrossRef]
  43. Niesen, J.G.; Blaabjerg, F.; Mohan, N. Control strategies for dynamic voltage restorer compensating voltage sags with phase jump. In Proceedings of the 16th Annual IEEE Applied Power Electronics Conference and Exposition, Anaheim, CA, USA, 4–8 March 2001; Volume 2, pp. 1267–1273. [Google Scholar]
  44. Szcześniak, P. Comparison of control methods for a dynamic voltage restorer using a three-phase matrix converter. Simulation 2016, 92, 1053–1063. [Google Scholar] [CrossRef]
  45. Mohammadi, B.; Rabiei, A.; Moradi-Dalvand, M.; Mobayen, S. Online inter-area oscillation monitoring in power systems using PMU data and Prony analysis. Int. J. Phys. Sci. 2011, 6, 267–5272. [Google Scholar]
Figure 2. (a) BSFCL circuit; (b) test system for analytical analysis; (c) SC and fault current.
Figure 2. (a) BSFCL circuit; (b) test system for analytical analysis; (c) SC and fault current.
Sensors 21 01615 g002aSensors 21 01615 g002b
Figure 3. Power circuit of DVR.
Figure 3. Power circuit of DVR.
Sensors 21 01615 g003
Figure 4. Proposed structure.
Figure 4. Proposed structure.
Sensors 21 01615 g004
Figure 5. Operation of chopper in the fault condition, (a) gating signal of T, (b) T is ON, and (c) T is OFF.
Figure 5. Operation of chopper in the fault condition, (a) gating signal of T, (b) T is ON, and (c) T is OFF.
Sensors 21 01615 g005
Figure 6. (a) PLL diagram, (b) Control strategy DVR during fault, (c) Control strategy of the boost chopper during fault, (d) phasor diagram of DVR voltage injection.
Figure 6. (a) PLL diagram, (b) Control strategy DVR during fault, (c) Control strategy of the boost chopper during fault, (d) phasor diagram of DVR voltage injection.
Sensors 21 01615 g006
Figure 7. Simulated system.
Figure 7. Simulated system.
Sensors 21 01615 g007
Figure 8. (a) Fault current in case A, (b) voltage of PCC in case A.
Figure 8. (a) Fault current in case A, (b) voltage of PCC in case A.
Sensors 21 01615 g008
Figure 9. (a) Fault current in case B, (b) voltage of PCC in case B.
Figure 9. (a) Fault current in case B, (b) voltage of PCC in case B.
Sensors 21 01615 g009
Figure 10. (a) load voltage, (b) DVR port injected voltage, (c) PCC voltage and, (d) capacitor voltage during fault, in case C.
Figure 10. (a) load voltage, (b) DVR port injected voltage, (c) PCC voltage and, (d) capacitor voltage during fault, in case C.
Sensors 21 01615 g010aSensors 21 01615 g010b
Figure 11. (a) The load current and, (b) fault current of faulted feeder (F2) during fault operation mode in case C.
Figure 11. (a) The load current and, (b) fault current of faulted feeder (F2) during fault operation mode in case C.
Sensors 21 01615 g011
Figure 12. (a) The current of common loads in F1, (b) SC coil current, (c) enlargement SC coil current during fault in case C.
Figure 12. (a) The current of common loads in F1, (b) SC coil current, (c) enlargement SC coil current during fault in case C.
Sensors 21 01615 g012
Table 1. Parameters of study system.
Table 1. Parameters of study system.
ParametersValue
GridSupply voltage(Vs)20 kV
Frequency (f)50 Hz
Rs0.05 Ω
Ls1 mH
Step down
transformer
20 kV/6.6 kV
5 MVA
LineLine resistance (R)0.2 (Ω/km)
Line reactance (X)0.4 (Ω/km)
Length of feeder120 km
Length of feeder 210 km
LoadImpedance of common load 1 MVA, PF = 0.9 lag
Impedance of sensitive load 1 MVA, PF = 0.8 lag
Proposed StructureDVR port transformers 4 kV/4 kV, 2 MVA
Capacitor4 kV,1000 uF
SC inductance100 mH
Lf25 uH
Cf50 uF
frequency switching of chopper2 kH
Table 2. Comparison of harmonic components of PCC voltage in cases B and C.
Table 2. Comparison of harmonic components of PCC voltage in cases B and C.
Order of HarmonicsCase BCase C
10.58391
20.02890.0001
30.00880.0001
40.01550.0001
50.10870.0363
60.03030.0001
70.04890.0301
80.02190.0001
90.01210.0006
100.01620.0001
110.03810.0261
120.01890.0001
130.03160.0214
140.02820.0001
150.04310.0086
THD25.76%6.9%
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Firouzi, M.; Mobayen, S.; Kartijkolaie, H.S.; Nasiri, M.; Chen, C.-C. Protection of Sensitive Loads in Distribution Systems Using a BSFCL-DVR System. Sensors 2021, 21, 1615. https://doi.org/10.3390/s21051615

AMA Style

Firouzi M, Mobayen S, Kartijkolaie HS, Nasiri M, Chen C-C. Protection of Sensitive Loads in Distribution Systems Using a BSFCL-DVR System. Sensors. 2021; 21(5):1615. https://doi.org/10.3390/s21051615

Chicago/Turabian Style

Firouzi, Mehdi, Saleh Mobayen, Hossein Shahbabaei Kartijkolaie, Mojtaba Nasiri, and Chih-Chiang Chen. 2021. "Protection of Sensitive Loads in Distribution Systems Using a BSFCL-DVR System" Sensors 21, no. 5: 1615. https://doi.org/10.3390/s21051615

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop