Sustainable Energy Grids & Networks ( IF 5.4 ) Pub Date : 2021-07-26 , DOI: 10.1016/j.segan.2021.100522 Manoj Kumar Senapati 1 , Saumendra Sarangi 2
Three-phase fault and load encroachment are balanced phenomena. A load encroachment function is incorporated in distance relay to improve the security of protection scheme, confuses with three-phase fault during high reactive loading condition. Zone 3 malfunction during such a situation often causes cascade line tripping leading to wide-area disturbance. In this work, voltage phasors of selected buses from a wide area measurement system (WAMS) are used to prevent zone 3 maloperation of a distance relaying scheme during load encroachment. The change in magnitude and phase of bus voltages are applied to discriminate three-phase fault from load encroachment. Performance of the proposed method is tested with New England 39 bus and IEEE 118 bus system simulated in EMTDC/PSCAD. Results show high accuracy as well as the speed of operation, is very fast of the proposed method.