当前位置: X-MOL 学术IEEE Trans. Dielect Elect. Insul. › 论文详情
Our official English website, www.x-mol.net, welcomes your feedback! (Note: you will need to create a separate account there.)
An Improved Electrochemical Method for Moisture Determination in Mineral Oil
IEEE Transactions on Dielectrics and Electrical Insulation ( IF 3.1 ) Pub Date : 2020-12-01 , DOI: 10.1109/tdei.2020.009016
M. Lyutikova

The paper presents an option to improve the method for water determination using a transformer oil moisture meter, which is widely used in power grid laboratories to monitor water in oil. It is found that the older the oil, the less convergence, and reproducibility of the water analysis results in oil obtained by two methods - coulometric titration with Karl Fischer reagent and electrochemical method with electrolysis of water on a sensitive element. It is shown how the sorption of the amount of water from the oil matrix is improved by transformer oil sample heating to 80 °C, which positively affects the metrological characteristics of the electrochemical method for determining water in liquid dielectrics.

中文翻译:

矿物油水分测定的改进电化学方法

本文提出了一种改进使用变压器油水分仪测定水分的方法的选项,变压器油水分仪广泛用于电网实验室监测油中的水分。发现油越老,水分析结果的收敛性和重现性越差,水分析结果通过两种方法获得——使用卡尔费休试剂的库仑滴定法和在敏感元件上电解水的电化学方法。显示了如何通过将变压器油样品加热到 80 °C 来改善从油基质中吸水的量,这对测定液体电介质中水的电化学方法的计量特性产生了积极影响。
更新日期:2020-12-01