10 kV AC test verification of the high temperature superconducting fault current limiter with bias magnetic field
Cryogenics ( IF 2.1 ) Pub Date : 2020-12-01 , DOI: 10.1016/j.cryogenics.2020.103195
Yujun Dong , Jiahui Zhu , Defu Wei , Wei Chen , Qingqing Du , Ke Zhang , Panpan Chen , Kun Lu , Hao Jiang , Shuai Wang , Jiaxing Liu , Tie Guo , Kaizhong Ding

Abstract Under the support of the China State Grid Corporation Science and Technology Project, a set of 10 kV superconducting fault current limiter (SFCL) with bias magnetic field including a high temperature superconducting a low inductance unit, a double split reactor, a fast breaker and its control system is designed and assembled in Hushitai high voltage center of Electric Power Research Institute of State Grid Liaoning Electric Power Co., Ltd. The 10 kV dedicated test including high voltage test, phase to phase short circuiting fault test, quench resistance measurement, quench recovery time measurement were performed in December 2019. The fault current distribution and voltage test results during the phase to phase short-circuit fault of the SFCL are presented and analyzed. Test results indicate that current limiting resistance of SFCL unit is about 1.21 Ω within 10 ms fault time. Those results meet the design requirement.

中文翻译:

偏磁场高温超导故障限流器10 kV交流试验验证

测试结果表明,SFCL 单元的限流电阻在 10 ms 故障时间内约为 1.21 Ω。这些结果满足设计要求。