Applied Thermal Engineering ( IF 6.4 ) Pub Date : 2020-03-19 , DOI: 10.1016/j.applthermaleng.2020.115219
C. McCague , W. Huttema , A. Fradin , M. Bahrami

Water adsorbent AQSOATM FAM-Z02 (Z02) coatings and pellets were evaluated in our custom-built lab-scale sorption chiller with two adsorber beds. Two finned-tube heat exchangers (HEX) (4.08 L) were coated with Z02 by Mitsubishi Plastics and compared with two other HEX that were packed with Z02 pellets. When tested with 15, 30, 30 and 90 °C operating temperatures for the evaporator, condenser, adsorption and desorption, and 5 to 30 min cycle times, the sorption chiller had a peak volumetric specific cooling power of 90 ± 5 kW/m3 with Z02-coated HEX compared to 59 ± 2 kW/m3 for HEX packed with Z02 pellets. The specific cooling power (SCP) and coefficient of performance (COP) were greater for Z02 coatings compared to pellets.



中文翻译:

FAM-Z02涂层和颗粒的实验室规模吸附式冷却器的比较

在我们具有两个吸附床的定制实验室规模吸附式冷却器中,对水吸附剂AQSOA TM FAM-Z02(Z02)的涂层和颗粒进行了评估。Mitsubishi Plastics用Z02涂覆了两个翅片管热交换器(HEX)(4.08 L),并将其与装有Z02颗粒的另外两个HEX进行了比较。在15、30、30和90°C的蒸发器,冷凝器,吸附和解吸操作温度以及5至30分钟的循环时间下进行测试时,吸附式冷却器的容积比冷却峰值功率为90±5 kW / m 3 Z02包覆的HEX相比,而用Z02颗粒填充的HEX则为59±2 kW / m 3。与颗粒相比,Z02涂层的比冷却功率(SCP)和性能系数(COP)更大。